Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00468 INSP-Conference9/23/20139/23/20139/23/2013 3:42:36 PMPDONE
Brian and I went over review comments and other misc items
FIR13-00095 INSP-Final Inspection9/23/20139/23/20139/23/2013 3:33:23 PMPCANC
Duplicate inspection
FIR13-00095 INSP-Final Inspection9/20/20139/23/20139/23/2013 2:52:06 PMAFAIL
The "well" needs to be installed at the FDC riser and provide tag for the backflow preventor and a head wrench.
FIR13-00113 INSP-Final Inspection9/19/20139/23/20139/23/2013 2:50:51 PMAFAIL
Need the two duct smoke detectors to shut down the hvac units immediately to final this permit.
BLD12-01914 FIRE-Final Inspection9/20/20139/23/20139/23/2013 8:34:55 AMAPASS
Area 2A life safety passed.