Inspections for the day of: Monday, September 23, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01183 ELE-Aging Inspection9/23/20139/23/20139/25/2013 1:48:06 PM DONE
Homeowner will call for final
ELE13-02453 Electrical Rough-In9/20/20139/23/20139/23/2013 2:32:49 PMPNR
After 3:00 pm please-John Phone #: ###-#### Not ready
ELE11-02093 Final9/19/20139/23/20139/23/2013 2:06:58 PMPPASS
Please call homeowner about 30 minutes early.
###-#### or ###-#### Phone #: ###-#### >> Inspection requested via web by William Andrews job complete, final ok
ELE13-02612 Final9/22/20139/23/20139/23/2013 1:39:33 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Dan Hobdey correction done, final ok
ELE13-01948 Final9/20/20139/23/20139/23/2013 1:27:23 PMAPASS
Phone #: ###-#### >> Inspection requested via web by David Nelson final ok
ELE13-02497 Final9/22/20139/23/20139/23/2013 12:35:32 PMAFAIL
panel changed Phone #: ###-#### >> Inspection requested via web by Robert Carter NEC 110.26(A) Working space for service equipment, NEC 408.4 complete panel directory circiuts #13 & 19 Bond hot and cold water pipes at water heater
ELE13-02627 Final9/23/20139/23/20139/23/2013 11:02:19 AMPCANC
Contact: Brian Gee, fairly late afternoon inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
ELE13-02428 Conference9/19/20139/23/20139/23/2013 10:41:12 AMADONE
mike Phone #: ###-#### Discussed grounding for separately derived system,from generator with transfer switch.Common building grounding,supplemental electrode required
ELE13-02619 Electrical Rough-In9/20/20139/23/20139/23/2013 10:25:49 AMAPASS
need ok to cover in two new bathrooms Phone #: ###-#### >> Inspection requested via web by Dan Hobdey rough-in ok cover
ELE13-02617 Final9/20/20139/23/20139/23/2013 9:45:49 AMAPASS
Contact Vince ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate final ok
ELE13-02617 Electrical Rough-In9/23/20139/23/20139/23/2013 9:44:04 AMPPASS
Contact Vince ###-#### Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok
ELE13-02232 Rough-In Permanent Service9/19/20139/23/20139/23/2013 9:07:08 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Tracy Robertson rough-in p/s u/g n ok
ELE13-01457 Final9/23/20139/23/20139/23/2013 8:25:11 AMAFAIL
We are requesting a partial final. This would be a final for the building only with site to follow later. Contact is Jay Sprik. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery NEC 210.8(B) All 125 Volt single phase, 15 and 20 ampere receptacles in kitchens shall have GFCI protection for personal. NEC 422.51 Cord and plug connected vending machines require GFCI protection NEC 406.(B) listed weather resistant receptacle, roof top service receptacle