ELE13-01131
| ELE-Aging Inspection | 9/23/2015 | 9/23/2015 | 9/25/2015 11:11:09 AM | | CANC |
|
|
too busy
|
ELE12-01900
| ELE-Aging Inspection | 9/23/2015 | 9/23/2015 | 9/25/2015 11:10:43 AM | | CANC |
|
|
too busy
|
ELE15-02825
| Electrical Rough-In | 9/22/2015 | 9/23/2015 | 9/23/2015 2:58:14 PM | P | PASS |
|
|
Phone #: ###-#### Very nice work no conference needed. M. bath, new closet, kitchen remodel, new utility room rough in ok cover
|
ELE15-02914
| Final | 9/18/2015 | 9/23/2015 | 9/23/2015 2:36:57 PM | P | PASS |
|
|
Please call homeowner, Leslie Criner; 30 min prior to arrival at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller Final ok
|
ELE15-03039
| Electrical Rough-In | 9/22/2015 | 9/23/2015 | 9/23/2015 2:05:31 PM | P | PASS |
|
|
The Suite # is 109. It is between Edible Arrangements and Blimpie. The key is in the mailbox on the wall and is marked 108. Phone #: ###-#### Inspection requested via web by Craig Korell Wall dividing front area from dance area rough in ok cover.
|
ELE15-02264
| Final | 9/23/2015 | 9/23/2015 | 9/23/2015 1:49:31 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3 Patio receptacle not working unit 101
|
ELE15-02525
| Final | 9/23/2015 | 9/23/2015 | 9/23/2015 1:01:58 PM | P | FAIL |
|
|
The side garage door is unlocked for inspections Phone #: ###-#### Inspection requested via web by Brad Baker 210.8(A)(6)- All receptacles located in kitchen that serve counter top area shall have GFCI protection. 422.30- All appliances shall have a disconnecting means.
|
ELE15-02880
| Rough-In Permanent Service | 9/23/2015 | 9/23/2015 | 9/23/2015 12:45:19 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE15-01067
| Electrical Rough-In | 9/23/2015 | 9/23/2015 | 9/23/2015 12:22:30 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Discussed with contractor required show window receptacles, He stated conduits in place asked to check on final. Showroom grid rough in ok cover
|
ELE15-03038
| Rough-In Permanent Service | 9/22/2015 | 9/23/2015 | 9/23/2015 11:10:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon Underground to service not in at time of inspection Rough in ok cover p/s u/g n ok
|
ELE15-01892
| Final | 9/22/2015 | 9/23/2015 | 9/23/2015 10:30:10 AM | A | PART |
|
|
Mark-wants Temp CO Phone #: ###-#### North side ventalation provided, south not ventalated. All electrical located above classified areas. Need finish sign and pour seal offs for paint booth. Temp final ok
|
ELE15-03030
| Temporary Service | 9/23/2015 | 9/23/2015 | 9/23/2015 9:54:20 AM | A | FAIL |
|
|
call dene with any questions thank you Phone #: ###-#### Inspection requested via web by kim grundhauser 250.50- Where grounding electode system is not present one shall be provided. Must see connection to grounding electrode system prior to connection of service
|
ELE15-02482
| Electrical Rough-In | 9/22/2015 | 9/23/2015 | 9/23/2015 9:09:21 AM | A | PASS |
|
|
Ceiling cover Phone #: ###-#### Inspection requested via web by Thomas Jenkins Grid rough in ok cover
|
ELE15-02482
| Electrical Rough-In | 9/23/2015 | 9/23/2015 | 9/23/2015 9:07:31 AM | P | FAIL |
|
|
Ceiling cover Phone #: ###-#### Inspection requested via web by Thomas Jenkins 314.16- Boxes shall be of an approved size to provide free space for all enclosed conductors. Prefab wall behind cook station.
|
ELE15-02035
| Final | 9/22/2015 | 9/23/2015 | 9/23/2015 8:22:39 AM | A | PASS |
|
|
Roger Phone #: ###-#### Final ok
|