Inspections for the day of: Friday, September 23, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01652 Electrical Rough-In9/23/20169/23/20169/23/2016 1:42:39 PMPPASS
Bonding of fountain cans. Contact John @ ###-#### about 30mins prior to inspection. Phone #: ###-#### Inspection requested via web by Kristopher Wilson
Bonding as noted rough in ok cover
ELE16-02722 Electrical Rough-In9/23/20169/23/20169/23/2016 12:39:11 PMPPASS
Ceiling inspection! Call for access Phone #: ###-#### Inspection requested via web by steve sellers Grid rough in ok cover
ELE16-01838 Final9/23/20169/23/20169/23/2016 11:55:39 AMPFAIL
Branch Circuit Panels, Branch Circuits, Equip. Conn.,Outlets, Office Furniture All LV systems Phone #: ###-#### Inspection requested via web by Tom Betty
110.3- Connect furniture as per manufacturers instructions. Furniture fed by panel 41A circuits 63, 65 not working.
300.15- All boxes containing cables shall be covered. Some blinds back ordered wiring not in boxes operates at 15 volt DC. Tie up and store neatly for future installation. Secure covers on furniture several loose.
300.21- Seal large 4x4 hole on interior of electrical room. Seal floor and ceiling when temp wiring has been removed.
392.60- Ladder racks for data cabling shall be bonded.
605.5- Connections to some furniture not complete and furniture missing.
ELE15-01348 Final9/23/20169/23/20169/23/2016 11:24:43 AMAFAIL
Branch Circuit Panels, Branch Circuits, Equip. Conn. , Outlets,
Level 4 Stack 1,2,3,4 Phone #: ###-#### Inspection requested via web by Tom Betty
110.3- Connect furniture as per manufacturers instructions. Furniture fed by panel 41A circuits 63, 65 not working.
300.15- All boxes containing cables shall be covered. Some blinds back ordered wiring not in boxes operates at 15 volt DC. Tie up and store neatly for future installation. Secure covers on furniture several loose.
300.21- Seal large 4x4 hole on interior of electrical room. Seal floor and ceiling when temp wiring has been removed.
392.60- Ladder racks for data cabling shall be bonded.
605.5- Connections to some furniture not complete and furniture missing.
ELE16-01838 Final9/22/20169/23/20169/23/2016 11:10:28 AMACANC
Contact Brandon Robinson for level 4 TI lighting final. Phone #: ###-#### Inspection requested via web by Tom Betty
Needed note of prewalk of level 4 stack 1, 2, 3, 4. See conference
ELE16-01838 Conference9/23/20169/23/20169/23/2016 11:09:34 AMPDONE
Contact Brandon Robinson for level 4 TI lighting final. Phone #: ###-#### Inspection requested via web by Tom Betty
Level 4 stack 1, 2, 3,4 lighting complete
ELE16-00151 Electrical Rough-In9/22/20169/23/20169/23/2016 9:35:12 AMAPASS
Ceiling cover inspection VRT level. Contact Eric Gibson ###-####. If he does not answer contact Toby Groves ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
VRT grid complete rough in ok cover
ESC16-00756 Site Preparation9/23/20169/23/20169/23/2016 8:49:50 AMPPASS
Fully landscaped. Final ok
ELE16-02484 Electrical Rough-In9/21/20169/23/20169/23/2016 8:44:17 AMAPASS
Randy. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Ceiling grid rough in ok cover