Inspections for the day of: Friday, September 23, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00305 INSP-Sprinkler Rough-in9/22/20169/23/20169/23/2016 10:51:35 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping located on level 5 complete, overhead fire sprinkler piping located on level 5 approved for cover.
FIR16-00210 INSP-Final Inspection9/23/20169/23/20169/23/2016 10:50:30 AMPPASS
Final inspection for dry standpipes complete, knox caps are on order and will be installed when received.
FIR16-00017 INSP-Final Inspection9/20/20169/23/20169/23/2016 10:47:14 AMPPASS
Final fire sprinkler inspection passed/complete, hydrostatic test was completed on 06MAY2016
FIR16-00518 INSP-Sprinkler Rough-in9/22/20169/23/20169/23/2016 9:27:45 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover. Pendant head located in the dining area is less than 12 inches from heat source grid mounted heat register, sprinkler head will be changed from a 155 degree to a 200 degree.