FIR19-00690
| INSP-Final Inspection | 9/23/2019 | 9/23/2019 | 9/23/2019 2:58:14 PM | P | PASS |
|
|
Final fire alarm inspection for area of work complete.
|
FIR19-00690
| INSP-Alarm Testing | 9/19/2019 | 9/23/2019 | 9/23/2019 2:57:51 PM | P | DONE |
|
|
Fire alarm testing is complete.
Derek Ellis will be performing the inspection. Phone #: ###-#### Inspection requested via web by Bret Anderson
|
FIR18-00444
| INSP-Alarm Testing | 9/22/2019 | 9/23/2019 | 9/23/2019 2:33:07 PM | P | CANC |
|
|
Rescheduled to coincide with fire pump commissioning, per point of contact this request is cancelled and point of contact will provide the reschedule.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR19-00255
| INSP-Final Inspection | 9/23/2019 | 9/23/2019 | 9/23/2019 2:31:16 PM | P | PASS |
|
|
Previously noted items have been corrected, final fire alarm inspection for area of work complete.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD19-02025
| FIRE-Final Inspection | 9/23/2019 | 9/23/2019 | 9/23/2019 10:55:41 AM | P | PASS |
|
|
Fire sprinkler modifications are complete, no fire alarm modifications, fire extinguishers are placed with current inspection tags. Final life fire safey inspection for area of work complete.
Will Phone #: ###-####
|
FIR19-00583
| INSP-Sprinkler Rough-in | 9/23/2019 | 9/23/2019 | 9/23/2019 10:31:25 AM | P | FAIL |
|
|
Sidewalls above ceiling grid in classroom 101 are more than 12 foot off of wall, heads are overspaced. Hardlids have been installed before rough in inspection has been performed, cover has not been approved. Mechanical room 114 has heads installed under duct work, still need heads above duct work 1 to 6 inches from bottom of deck, no fire sprinkler heads above duct work.
Contact Hunter Anderson ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|