Inspections for the day of: Tuesday, September 24, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00023 FIRE-Final Inspection9/23/20029/24/20029/24/2002 12:00:00 AMANR
inspection was actually just a conference. I went over door hardware issues with the owner, fire extinguisher and possible hvac automatic shutdown 9/24/2002 10:25:15 AM
BLD02-00023 FIRE-Final Inspection9/23/20029/24/20029/24/2002 12:00:00 AMANR
inspection was actually just a conference. I went over door hardware issues with the owner, fire extinguisher and possible hvac automatic shutdown 9/24/2002 10:25:15 AM
BLD02-01720 FIRE-Conference9/23/20029/24/20029/24/2002 12:00:00 AMADONE
spoke with the contractor about location of the new duct smoke detectors. 9/24/2002 9:32:54 AM
BLD02-00745 FIRE-Final Inspection9/24/20029/24/20029/24/2002 12:00:00 AMPFAIL
the clip in supports for the sprinkler heads still are not clipped onto the t-bar correctly 9/24/2002 9:34:03 AM
FIR02-00296 INSP-Final Inspection9/24/20029/24/20029/24/2002 12:00:00 AMPFAIL
Pendants in rooms 002 and 038 are overspaced, head in corr. 031 is blocked by a exit sign and there is no sprinkler coverage by Meds 019 9/24/2002 9:47:16 AM
FIR02-00364 INSP-Sprinkler Rough-in/Hydro9/23/20029/24/20029/24/2002 12:00:00 AMPPASS
add sprinkler head in entry and provide a hanger on pendant over cooler 9/24/2002 3:28:03 PM
BLD01-02575 FIRE-Final Inspection9/23/20029/24/20029/24/2002 12:00:00 AMPFAIL
no approved plans on site. I did not inspect project 9/24/2002 3:16:30 PM
FIR02-00151 INSP-Final Inspection9/23/20029/24/20029/24/2002 12:00:00 AMPFAIL
strobe overspaced in n.e. corner of building #4, provide weatherproof listing for the A/V installed on the exterior wall, provide revised battery calculations for the a/v's since what is installed is not what was submitted, wire the circuits to match the plans submitted, clean up the wiring in the fire alarm panel, the inspection was stopped due to the problems listed above 9/24/2002 2:31:26 PM