Inspections for the day of: Wednesday, September 24, 2003.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00335 FIR-Aging Inspection9/24/20039/24/20039/24/2003 12:00:00 AM NR
Per Jim Danes the work is complete. He just needs to cordinate access and will call in the inspection next week 9/25/2003 12:57:59 PM
FIR03-00526 INSP-Sprinkler Rough-in/Hydro9/24/20039/24/20039/24/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 9/24/2003 at 7:23:06 AM. Contact: ###-####.
FIR03-00216 INSP-Final Inspection9/24/20039/24/20039/24/2003 12:00:00 AMPFAIL
duct detector signals arrive at the monitoring station as gatevavles, pull in lobby comes in as pull - fire, smoke in lobby comes in as general alarm, update the map to show the duct detectors, verify that the 8521 address is reported separatly 9/24/2003 2:54:13 PM