Inspections for the day of: Monday, September 24, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03282 Electrical Rough-In9/24/20079/24/20079/24/2007 3:54:06 PMPPART
R.I. Walls. Please call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson walls ok
ELE07-02963 Electrical Rough-In9/24/20079/24/20079/24/2007 3:20:51 PMPPART
Underground Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton
parking lot u/g ok still needs inspection for east & west pole lights u/g
ELE07-03301 Electrical Rough-In9/24/20079/24/20079/24/2007 2:53:00 PMPNH
john Phone #: ###-#### notice posted called no response left message
ELE07-03222 Electrical Rough-In9/24/20079/24/20079/24/2007 2:31:11 PMPNH
Steve ###-#### notice posted called
ELE07-03192 Electrical Rough-In9/21/20079/24/20079/24/2007 2:05:07 PMPCANC
Mike, late p.m. please call 1st; Phone #: ###-#### or ###-#### Internet Inspection Request from: Cathy Weisshaupt see added conference
ELE07-03192 Conference9/24/20079/24/20079/24/2007 2:04:37 PMPDONE
Mike, late p.m. please call 1st; Phone #: ###-#### or ###-#### Internet Inspection Request from: Cathy Weisshaupt conf. ok
BCC no violations retained prior owner changed the P/S without permit or inspection and is in violation of NEC no grds, no bonding, and wire and meter not 200 amp rated
ELE07-02988 Rough-In Permanent Service9/24/20079/24/20079/24/2007 1:17:09 PMPPASS
Thank You!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
remove drain from below p/s, protect cables by attic access r/i p/s u/g new ok
ELE07-02987 Rough-In Permanent Service9/24/20079/24/20079/24/2007 1:15:58 PMPPASS
Thank You!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i p/s u/g new ok
ELE07-03245 Rough-In Permanent Service9/21/20079/24/20079/24/2007 11:20:01 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn r/i p/s u/g new ok
ELE07-03244 Electrical Rough-In9/24/20079/24/20079/24/2007 10:53:09 AMAPART
TRENCH DEPTH INSP. ON SWIMMING POOL CONTACT JACK Phone #: ###-#### Internet Inspection Request from: Emmet Bushman u/g conduit and light bond ok, no E grid or pool cover bond
ELE07-02611 Electrical Rough-In9/24/20079/24/20079/24/2007 10:30:26 AMAFAIL
CHECK GROUND RODS---MAIN BREAKER Phone #: ###-#### Internet Inspection Request from: JAMES GARCES called left message protect #8 GEC, needs conn for GEC, bonding pool equip tie #8 together
ELE07-03289 Electrical Rough-In9/21/20079/24/20079/24/2007 10:03:50 AMAPASS
james Phone #: ###-#### ok see added final
ELE07-03289 Final9/24/20079/24/20079/24/2007 10:03:11 AMAPASS
james Phone #: ###-#### ok
ELE07-02016 Final9/21/20079/24/20079/24/2007 9:49:13 AMAFAIL
Randy''s cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher cords buried and used as fixed wiring and manufactured outdoor cabinet not listed
ELE07-03191 Electrical Rough-In9/21/20079/24/20079/24/2007 9:16:35 AMAPART
Tom; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
u/g conduit and boxes
ELE07-00573 Electrical Rough-In9/20/20079/24/20079/24/2007 8:36:40 AMAPART
Scheduled by a contractor via Hello! on 9/20/2007 at 3:21:10 PM. Contact: ###-####. ceilings anop