Inspections for the day of: Wednesday, September 24, 2008.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01055 ELE-Aging Inspection9/24/20089/24/200810/1/2008 8:40:04 AM DONE
ELE08-01461 Final9/24/20089/24/20089/24/2008 3:36:52 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton called contr will reschedule
ELE08-02597 Electrical Rough-In9/24/20089/24/20089/24/2008 3:24:45 PMPPART
This is a trench inspection for the underground electrical conduit for the remodeled drive-thru area. Need inspected so we can cover. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok
ELE08-01683 Temporary Service9/24/20089/24/20089/24/2008 2:57:38 PMPPART
Contact Chris Carmine. Inspection of temporary power. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong t/s from original t/s ok
ELE08-00026 Electrical Rough-In9/24/20089/24/20089/24/2008 2:33:28 PMPPART
kenneth - after 2 please Phone #: ###-#### see added p/s
ELE08-00026 Permanent Service9/24/20089/24/20089/24/2008 2:33:10 PMPPASS
kenneth - after 2 please Phone #: ###-#### p/s u/g new ok
ELE08-02400 Final9/23/20089/24/20089/24/2008 1:40:47 PMPPASS
this is ready Phone #: ###-#### Internet Inspection Request from: gary batten
ELE08-02167 Electrical Rough-In9/24/20089/24/20089/24/2008 12:47:51 PMPPART
Contact is Andy. Please inspect underslab electrical. Phone #: ###-#### Internet Inspection Request from: David Bonner
all u/g inside of building ok
ELE08-02562 Electrical Rough-In9/24/20089/24/20089/24/2008 12:14:42 PMPPART
Scheduled by a contractor via Hello! on 9/24/2008 at 7:04:56 AM. Contact: ###-####. walls ok 3rd floor numbers 312, and 313
ELE08-02600 Electrical Rough-In9/23/20089/24/20089/24/2008 11:05:52 AMAFAIL
contact: Bob Schroder Phone #: ###-#### Internet Inspection Request from: Julie Schroder called corr210.52(B) din rm shall be on SABC, 250.52(A)(1) or 104(A)(1) grd or bond water too service not subpanel, 344.46 and 300.10&12 needs bushings for rigid nipple 4 locknuts, size wire to subpanel to T310.16 3 cu or 1 alum needs connectors for cables and seal unused KOs subpanel
ESC08-00720 General Inspection9/24/20089/24/20089/24/2008 11:00:16 AMAPART
site ok
ELE08-02602 Electrical Rough-In9/23/20089/24/20089/24/2008 10:12:35 AMAPASS
jay Phone #: ###-#### r/i ok
ESC08-00362 General Inspection9/24/20089/24/20089/24/2008 10:07:53 AMAPART
ok
ESC08-00816 General Inspection9/24/20089/24/20089/24/2008 9:47:02 AMAPART
ok front clean landscape work in back
ELE08-02590 Conference9/22/20089/24/20089/24/2008 9:36:58 AMADONE
David Phone #: ###-#### went over NEC requirements for subpanel , kit. and din rm
ESC06-01785 General Inspection9/24/20089/24/20089/24/2008 8:46:04 AMAPART
ok
ELE08-01979 Conference9/23/20089/24/20089/24/2008 8:43:07 AMAFAIL
John- call 30 prior to going Phone #: ###-#### owner has already installed wiring , all messed up address kit circuits, din rm, range from sub panel. bed rm, and bath rm circuit 6" free length, outlet spacing in rooms and countertops, clearence for sub panel use only manufactures listed breakers, told owner he needs how too books and access to 2008 NEC
ELE08-02552 Electrical Rough-In9/23/20089/24/20089/24/2008 8:07:55 AMAPART
kevin - groundwork Phone #: ###-####
electrode ok for dirt ,, shall terminate all GEC and water bonds to neutral bus