BLD07-02839
| FIRE-Final Inspection | 9/23/2008 | 9/24/2008 | 9/24/2008 4:33:28 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD07-02840
| FIRE-Final Inspection | 9/23/2008 | 9/24/2008 | 9/24/2008 4:32:57 PM | A | PASS |
|
|
Fire life safety finaled.
|
BLD07-02841
| FIRE-Final Inspection | 9/23/2008 | 9/24/2008 | 9/24/2008 4:32:12 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD07-02842
| FIRE-Final Inspection | 9/23/2008 | 9/24/2008 | 9/24/2008 4:31:33 PM | A | PASS |
|
|
Life safety finaled.
|
BLD07-02843
| FIRE-Final Inspection | 9/23/2008 | 9/24/2008 | 9/24/2008 4:30:29 PM | A | PASS |
|
|
Life safety inspection passed.
|
BLD07-02838
| FIRE-Final Inspection | 9/23/2008 | 9/24/2008 | 9/24/2008 4:29:29 PM | A | PASS |
|
|
Life safety passed.
|
BLD08-01679
| FIRE-Final Inspection | 9/24/2008 | 9/24/2008 | 9/24/2008 4:28:20 PM | P | FAIL |
|
|
Need to post one fire extinguisher within allowable travel distances, project related fire alarm permit must be finaled prior to final fire life safety approval.
|
FIR08-00621
| INSP-Final Inspection | 9/22/2008 | 9/24/2008 | 9/24/2008 4:25:49 PM | A | FAIL |
|
|
The fire alarm audible notification shall be a distinctive temporal pattern per NFPA 72 requirements. See also notes #4 and #5 on plan review comments.
|
FIR08-00239
| INSP-Sprinkler Rough-in/Hydro | 9/23/2008 | 9/24/2008 | 9/24/2008 4:19:58 PM | A | PART |
|
|
See areas on 3rd floor plan marked with today's date, noted two missing hangers, need EC coverage SW heads at the patios due to spacing (head legend does not indicate), pipe sizes on plan must match field install.
|
FIR08-00516
| INSP-Sprinkler Rough-in | 9/23/2008 | 9/24/2008 | 9/24/2008 11:17:56 AM | A | PART |
|
|
Verified correction notice items are complete per last inspection, pendent heads at the paint mixing room are the correct type however plan legend indicates 286 deg. heads and 155 deg. heads have been installed. Also need to adjust deck insulation blocking one upright head prior to final. Office areas are okay for cover at the drop ceilings.
|
BLD08-01679
| FIRE-Final Inspection | 9/23/2008 | 9/24/2008 | 9/24/2008 8:23:19 AM | A | CANC |
|
|
Can you please call with about a 30 min lead time? Phone #: ###-#### Internet Inspection Request from: Nick Downing Inspection cancelled from web by: Nick Downing
|
FIR08-00222
| INSP-Sprinkler Rough-in/Hydro | 9/23/2008 | 9/24/2008 | 9/23/2008 3:21:14 PM | A | CANC |
|
|
Final Inspection - Contact: Todd Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|