Inspections for the day of: Wednesday, September 24, 2008.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00428 FIR-Aging Inspection9/24/20089/24/20089/25/2008 11:25:15 AM NR
Work is in progress.
FIR08-00554 INSP-Final Inspection9/24/20089/24/20089/24/2008 4:37:59 PMPFAIL
Provide knox box, signal report and relocate/test the west manual pull station as discussed.
FIR08-00429 INSP-Sprinkler Rough-in/Hydro9/24/20089/24/20089/24/2008 3:43:09 PMPPASS
The underground hydro test passed.
BLD08-00952 FIRE-Final Inspection9/23/20089/24/20089/24/2008 3:42:00 PMAFAIL
See the city approved plans for the list of deficiencies.
FIR08-00222 INSP-Final Inspection9/23/20089/24/20089/24/2008 11:17:23 AMACANC
To be rescheduled with the fire alarm testing.
FIR08-00289 INSP-Final Inspection9/23/20089/24/20089/24/2008 11:16:54 AMACANC
To be rescheduled with the fire alarm testing.