Inspections for the day of: Monday, September 24, 2012.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00521 FIR-Aging Inspection9/24/20129/24/201210/1/2012 9:30:58 AM NR
Forwarded information to Scott for further action.
FIR12-00422 INSP-Sprinkler Rough-in9/24/20129/24/20129/24/2012 3:44:19 PMPPASS
The mechanical room sprinkler piping is ok to be covered.
BLD12-01863 FIRE-Conference9/24/20129/24/20129/24/2012 3:22:32 PMPDONE
I spoke to the general contractor about finding the fire alarm panel with multiple "Com Failure" troubles displayed. I let him know the fire alarm panel will need to be repaired prior to a final fire life safety sign off.
FIR12-00530 INSP-Final Inspection9/20/20129/24/20129/24/2012 3:18:16 PMPFAIL
All items tested ok except that the building plans and the fire alarm plans indicate a fire/moke damper to be installed. Currently only a fire damper is installed. Either the fire/smoke damper needs to be installed, as per plans, or verification provided that a fire "only" damper is ok and the fire alarm plans modified to show the change.
FIR11-00472 INSP-Final Inspection9/21/20129/24/20129/24/2012 2:32:39 PMPPASS
permit finaled
FIR12-00459 INSP-Sprinkler Rough-in9/24/20129/24/20129/24/2012 2:23:28 PMPPASS
rough-in passed
BLD12-02424 FIRE-Final Inspection9/24/20129/24/20129/24/2012 1:28:28 PMPPASS
life safety passed
FIR12-00477 INSP-Sprinkler Rough-in9/24/20129/24/20129/24/2012 12:54:55 PMPPASS
Sprinkler piping can be covered. Overhead rough-in for the exposed piping is passed. The approved plans indicate 155 dgree heads to be installed but 200 degree are actually installed, Per Tim Frost this change is acceptable but as-builts will be required prior to a final sign off.
FIR12-00186 INSP-Final Inspection9/21/20129/24/20129/24/2012 12:50:58 PMAFAIL
Permit is not ready for a final inspection. The alarm initiating devices have not been tested, ceiling tile has not been installed, wood has been installed above the ceiling at the pharmacy security door/track and an upright sprinkler head at the main exit is covered in tape.
FIR12-00021 INSP-Final Inspection9/21/20129/24/20129/24/2012 12:47:48 PMAPASS
Permit finaled
BLD10-01738 FIRE-Final Inspection9/19/20129/24/20129/24/2012 10:34:09 AMAPASS
Life safety passed
FIR10-00039 FIR-Aging Inspection9/24/20129/24/20129/24/2012 9:27:27 AM NR
Mary stated that she would try to get this scheduled for next week,
BLD12-01567 FIRE-Final Inspection9/21/20129/24/20129/24/2012 9:10:36 AMAPASS
life safety passed
FIR12-00089 FIR-Aging Inspection9/24/20129/24/20129/24/2012 9:07:13 AM NR
Per steve this inspection will be scheduled