FIR10-00521
| FIR-Aging Inspection | 9/24/2012 | 9/24/2012 | 10/1/2012 9:30:58 AM | | NR |
|
|
Forwarded information to Scott for further action.
|
FIR12-00422
| INSP-Sprinkler Rough-in | 9/24/2012 | 9/24/2012 | 9/24/2012 3:44:19 PM | P | PASS |
|
|
The mechanical room sprinkler piping is ok to be covered.
|
BLD12-01863
| FIRE-Conference | 9/24/2012 | 9/24/2012 | 9/24/2012 3:22:32 PM | P | DONE |
|
|
I spoke to the general contractor about finding the fire alarm panel with multiple "Com Failure" troubles displayed. I let him know the fire alarm panel will need to be repaired prior to a final fire life safety sign off.
|
FIR12-00530
| INSP-Final Inspection | 9/20/2012 | 9/24/2012 | 9/24/2012 3:18:16 PM | P | FAIL |
|
|
All items tested ok except that the building plans and the fire alarm plans indicate a fire/moke damper to be installed. Currently only a fire damper is installed. Either the fire/smoke damper needs to be installed, as per plans, or verification provided that a fire "only" damper is ok and the fire alarm plans modified to show the change.
|
FIR11-00472
| INSP-Final Inspection | 9/21/2012 | 9/24/2012 | 9/24/2012 2:32:39 PM | P | PASS |
|
|
permit finaled
|
FIR12-00459
| INSP-Sprinkler Rough-in | 9/24/2012 | 9/24/2012 | 9/24/2012 2:23:28 PM | P | PASS |
|
|
rough-in passed
|
BLD12-02424
| FIRE-Final Inspection | 9/24/2012 | 9/24/2012 | 9/24/2012 1:28:28 PM | P | PASS |
|
|
life safety passed
|
FIR12-00477
| INSP-Sprinkler Rough-in | 9/24/2012 | 9/24/2012 | 9/24/2012 12:54:55 PM | P | PASS |
|
|
Sprinkler piping can be covered. Overhead rough-in for the exposed piping is passed. The approved plans indicate 155 dgree heads to be installed but 200 degree are actually installed, Per Tim Frost this change is acceptable but as-builts will be required prior to a final sign off.
|
FIR12-00186
| INSP-Final Inspection | 9/21/2012 | 9/24/2012 | 9/24/2012 12:50:58 PM | A | FAIL |
|
|
Permit is not ready for a final inspection. The alarm initiating devices have not been tested, ceiling tile has not been installed, wood has been installed above the ceiling at the pharmacy security door/track and an upright sprinkler head at the main exit is covered in tape.
|
FIR12-00021
| INSP-Final Inspection | 9/21/2012 | 9/24/2012 | 9/24/2012 12:47:48 PM | A | PASS |
|
|
Permit finaled
|
BLD10-01738
| FIRE-Final Inspection | 9/19/2012 | 9/24/2012 | 9/24/2012 10:34:09 AM | A | PASS |
|
|
Life safety passed
|
FIR10-00039
| FIR-Aging Inspection | 9/24/2012 | 9/24/2012 | 9/24/2012 9:27:27 AM | | NR |
|
|
Mary stated that she would try to get this scheduled for next week,
|
BLD12-01567
| FIRE-Final Inspection | 9/21/2012 | 9/24/2012 | 9/24/2012 9:10:36 AM | A | PASS |
|
|
life safety passed
|
FIR12-00089
| FIR-Aging Inspection | 9/24/2012 | 9/24/2012 | 9/24/2012 9:07:13 AM | | NR |
|
|
Per steve this inspection will be scheduled
|