Inspections for the day of: Wednesday, September 24, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00654 ELE-Aging Inspection9/24/20149/24/20149/30/2014 4:40:53 AM CANC
ELE14-01901 Final9/24/20149/24/20149/24/2014 2:17:53 PMPPASS
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn ok final
ELE14-02656 Rough-In Permanent Service9/24/20149/24/20149/24/2014 1:50:56 PMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI ri ok, p/s u/g n ok
ELE14-01993 Electrical Rough-In9/24/20149/24/20149/24/2014 1:18:04 PMPPASS
Please call Clay when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan ri ok
ELE14-02654 Temporary Service9/23/20149/24/20149/24/2014 12:58:34 PMAFAIL
Phone #: ###-#### Inspection requested via web by Mike Cole called, no job id sticker, no address, no esc sign, fee due
ELE14-02574 Electrical Rough-In9/24/20149/24/20149/24/2014 12:21:45 PMPPASS
Mike-please call for access Phone #: ###-#### ri ok lower part only
ELE14-02363 Permanent Service9/23/20149/24/20149/24/2014 11:34:47 AMAFAIL
The access code is 6210, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren called, left message, ground rods not installed, access code not working
ELE14-01932 Final9/23/20149/24/20149/24/2014 11:05:26 AMAFAIL
Key is on top of meter main for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov called, NEC 210.52(E) shall provide rear receptacle
ELE14-01973 Final9/23/20149/24/20149/24/2014 11:01:34 AMAFAIL
Key is on top of meter main back of the house for access. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov called, left correction notice, NEC 110 shall install devices per instructions, 4-way switches top stairs, hall, pantry gfci shall operate, shall protect grounding electrode conductor
ELE14-01934 Electrical Rough-In9/23/20149/24/20149/24/2014 9:47:50 AMAFAIL
Underground inspection for feed from transformer to building. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery called, told to check with ipco, top of raceway only 24" below driveway, told that city usually not responsible for utility side of service
ELE14-02082 Electrical Rough-In9/23/20149/24/20149/24/2014 9:32:41 AMAPASS
Mike Phone #: ###-#### u/g ok south parking lot lighting
ELE14-01595 Electrical Rough-In9/23/20149/24/20149/24/2014 9:12:39 AMAPART
Contact: Wes Powell.. underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden south of bldg, west 1/2 u/g for lighting ok cover, talked about generator wiring from u/g
ELE14-02656 Rough-In Permanent Service9/23/20149/24/20149/24/2014 8:29:33 AMAFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI called, left correction notice, NEC 334.80 shall derate conductors over panel if more than 2 nm cables in hole, 334.23 shall protect nm cable within 6' of attic accesses, 210.52 shall install receptacle or floor box in 2' wall by pocket door, 300.4(A) edge of bored hole shall be 1 1/4" from face of framing member or add steel plate, BCC shall install wire into fan box