Inspections for the day of: Monday, September 24, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03582 Electrical Rough-In9/24/20189/24/20189/24/2018 3:40:40 PMPPASS
Lynn Phone #: ###-####
Rough in ok cover
ELE18-03582 Permanent Service9/24/20189/24/20189/24/2018 3:28:06 PMPPASS
Lynn Phone #: ###-####
p/s u/g n ok
ELE18-01571 Final9/23/20189/24/20189/24/2018 3:18:37 PMPFAIL
Phone #: ###-#### Inspection requested via web by Cameron Craven
210.8- All garage and accessory building receptacle outlets shall have GFCI protection. Garage door opener receptacle and shed receptacles. GFCI device must be installed below 6'7".
225.30- All accessory shall have a disconnecting means installed to disconnect all power in that structure. Shed needs a disconnecting means.
ELE18-03612 Final9/21/20189/24/20189/24/2018 2:46:11 PMPNH
Phone #: ###-#### Inspection requested via web by Same Electric
Called contact and said to asked for Thomas, I was unable to reach anyone inside to show area work is being performed. Waited at reception desk for 15 minutes. Recall when someone is available.
ELE18-02952 Electrical Rough-In9/24/20189/24/20189/24/2018 2:02:30 PMPPASS
Open ceiling inspection Phone #: ###-#### Inspection requested via web by steve ragan
Grid rough in ok cover
ELE18-02941 Electrical Rough-In9/24/20189/24/20189/24/2018 2:01:29 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Break area walls rough in ok cover
ELE18-01755 Final9/21/20189/24/20189/24/2018 1:04:37 PMAFAIL
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
210.52(D)- A receptacle outlet shall be installed adjacent to each bathroom vanity basin. LeveI 2 main bathroom.
BCC- Inspector shall have access to all areas for inspection. Level 2 common area and master bedroom provide access to all receptacles.
ELE18-03630 Temporary Service9/21/20189/24/20189/24/2018 10:06:27 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE18-03473 Temporary Service9/21/20189/24/20189/24/2018 10:06:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE18-03629 Temporary Service9/21/20189/24/20189/24/2018 10:05:36 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE18-02024 Final9/23/20189/24/20189/24/2018 9:22:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall Final ok
ELE18-02023 Final9/23/20189/24/20189/24/2018 9:14:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall Final ok
ELE18-02146 Final9/23/20189/24/20189/24/2018 9:13:34 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall Final ok
ELE18-01873 Final9/23/20189/24/20189/24/2018 9:12:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Todd Hall Final ok