Inspections for the day of: Monday, September 25, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02378 ELE-Aging Inspection9/25/20069/25/20069/26/2006 8:43:58 AM NR
wsuc
ELE06-02374 ELE-Aging Inspection9/25/20069/25/20069/26/2006 8:42:14 AM PART
called job will be ready for final in 2 or 3 weeks
ELE05-04325 Electrical Rough-In9/25/20069/25/20069/25/2006 5:01:53 PMPDONE
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
done 09-22-06
ELE06-01300 Final9/25/20069/25/20069/25/2006 5:01:10 PMPFAIL
mike Note: please call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left message, needs connector for romex at range hood
ELE06-02364 Electrical Rough-In9/25/20069/25/20069/25/2006 4:07:47 PMPPART
blake or ###-#### wayne ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie N E restrms walls hard ceilings, SE front wall
ELE06-03439 Electrical Rough-In9/25/20069/25/20069/25/2006 3:14:47 PMPPASS
stu; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley r/i ok
ELE06-03062 Final9/25/20069/25/20069/25/2006 2:19:23 PMPPASS
phil; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
ELE06-03235 Electrical Rough-In9/25/20069/25/20069/25/2006 1:53:35 PMPFAIL
eugene; Phone #: ###-#### Internet Inspection Request from: Barbara
corr. met owner part correction only job not ready 300.4 nail plates and 11/4", 210.52(A) 2ft wall 6ft 12ft, 314.16 box fill, 314.29 all boxes shall be accessible, 314.3&110.3(B) shall not use metallic fittings in non-metallic boxes, 110.12(A) seal all KOs, 250.148 grd all metal boxes, 200.42 calc circuits sq. ft and wet bar area, 310.16 shall not use #14 on 20 amp circuit, , BCC complete all wiring for r/i and all makeup shall be done COW
ELE06-03549 Conference9/21/20069/25/20069/25/2006 11:03:25 AMADONE
###-#### james--check in backyard if no anwer at door- no dogs on site
ELE06-03563 Conference9/22/20069/25/20069/25/2006 11:03:08 AMADONE
David ###-####
ELE06-02907 Rough-In Permanent Service9/22/20069/25/20069/25/2006 9:45:06 AMANR
mark - call 1/2hr prior to meet there; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley see added r/i
ELE06-02907 Electrical Rough-In9/25/20069/25/20069/25/2006 9:44:39 AMAPART
mark - call 1/2hr prior to meet there; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley garage still needs to complete makeup,