Inspections for the day of: Monday, September 25, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00094 INSP-Final Inspection9/22/20069/25/20069/25/2006 4:37:16 PMAFAIL
Phone line troubles failed to report. AC power loss and signals recieved remain to be verified, all other items tested okay.
BLD04-02808 FIRE-Final Inspection9/22/20069/25/20069/25/2006 3:15:57 PMPPASS
Corrections have been verified for completion, PFE's are provided as required, permit finaled.
BLD06-01589 FIRE-Final Inspection9/25/20069/25/20069/25/2006 3:13:40 PMPPART
Fire life safety is satisfactory pending final of project related alarm permit including completion of smoke and heat detectors at the top of the elevator hoistway. Temporary occupancy has been granted for the second floor portion of this tenant.
FIR06-00548 INSP-Sprinkler Rough-in9/22/20069/25/20069/25/2006 3:06:06 PMAPART
Sprinklers at the hard lid ceilings in the womens locker room as marked on approved plans are okay to cover.
MIS06-00222 FIR-Final9/22/20069/25/20069/25/2006 1:28:37 PMAFAIL
Remove the manual thumbturn at the main entry/exit door and provide signage stating "this door to remain unlocked while building is occupied", provide one fire extinguisher with current service tag mounted no higher than 48" AFF.
BLD06-01589 FIRE-Final Inspection9/22/20069/25/20069/25/2006 12:36:29 PMAFAIL
Project related fire alarm permit must be finaled prior to life safety final, need to relocate two and add one exit sign as discussed, need to install visual indicators at the main entry/exit door locks per review notes.
FIR06-00541 INSP-Final Inspection9/22/20069/25/20069/25/2006 12:33:52 PMAPART
Need to install a SD and HD at the top of the elevator hoistway per plan, also need to provide as-builts reflecting field modifications. Remaining fire alarm tested satisfactory.
FIR06-00638 INSP-Sprinkler Rough-in/Hydro9/21/20069/25/20069/25/2006 12:07:09 PMAPART
OH sprinkler rough-in at the remainder of hard lid areas for the sales floor are okay to cover as marked on approved plans. Drop ceiling areas are not yet complete.