BLD08-02001
| FIRE-Final Inspection | 9/25/2008 | 9/25/2008 | 9/25/2008 4:06:01 PM | P | FAIL |
|
|
One sprinkler pendant near the wall that hasa been removed is overspaced. A separate FIR permit will be required for this work. All life safety items will be ok to pass when the sprinkler issues have been addressed.
|
BLD08-02001
| FIRE-Alarm Testing | 9/25/2008 | 9/25/2008 | 9/25/2008 3:46:28 PM | P | CANC |
|
|
Wrong inspection type called in.
|
BLD08-01989
| FIRE-Conference | 9/25/2008 | 9/25/2008 | 9/25/2008 2:38:49 PM | P | CANC |
|
|
Wrong inspection type called in.
|
BLD08-01989
| FIRE-Final Inspection | 9/25/2008 | 9/25/2008 | 9/25/2008 2:38:26 PM | P | PASS |
|
|
Life safety passed.
|
FIR08-00608
| INSP-Alarm Testing | 9/25/2008 | 9/25/2008 | 9/25/2008 2:35:49 PM | P | FAIL |
|
|
The required module for the chippery has not been installed yet. Nobody was on site.
|
FIR08-00592
| INSP-Final Inspection | 9/25/2008 | 9/25/2008 | 9/25/2008 1:26:59 PM | P | PASS |
|
|
Permit finaled
|
BLD07-02106
| FIRE-Final Inspection | 9/24/2008 | 9/25/2008 | 9/25/2008 1:26:31 PM | A | PASS |
|
|
Life safety passed
|
BLD08-00952
| FIRE-Final Inspection | 9/24/2008 | 9/25/2008 | 9/25/2008 11:24:55 AM | A | PASS |
|
|
Life safety passed.
|
FIR08-00551
| INSP-Sprinkler Rough-in | 9/24/2008 | 9/25/2008 | 9/25/2008 11:24:01 AM | A | PART |
|
|
All of the outstanding rough-in issues have been taken care of except for verification from Tyco that the BB1 head installation still meets the manufacturers listing at the two areas of roof transitions. I have approved cover for all areas except for these two locations. Forrest France first addressed this issue on 9-22-2008. I let Ryan know that approved resubmittals will be required prior to a final inspection. My "redlined" city approved drawings are to be submitted to Bryan Johnson with this resubmittal. The building owner was witness to and part of the above conversations. I also found one pendant head in the west wing that was overspaced. Correct spacing will be verified at the final.
|
BLD08-01056
| FIRE-Alarm Testing | 9/23/2008 | 9/25/2008 | 9/25/2008 8:51:17 AM | A | FAIL |
|
|
Ansul and fire alarm test on the chippery kiosk was failed due to a module no being installed yet. Per the contractor the module will be installed tonight and the inspection called back in for tomorrow.
|