Inspections for the day of: Thursday, September 25, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-02001 FIRE-Final Inspection9/25/20089/25/20089/25/2008 4:06:01 PMPFAIL
One sprinkler pendant near the wall that hasa been removed is overspaced. A separate FIR permit will be required for this work. All life safety items will be ok to pass when the sprinkler issues have been addressed.
BLD08-02001 FIRE-Alarm Testing9/25/20089/25/20089/25/2008 3:46:28 PMPCANC
Wrong inspection type called in.
BLD08-01989 FIRE-Conference9/25/20089/25/20089/25/2008 2:38:49 PMPCANC
Wrong inspection type called in.
BLD08-01989 FIRE-Final Inspection9/25/20089/25/20089/25/2008 2:38:26 PMPPASS
Life safety passed.
FIR08-00608 INSP-Alarm Testing9/25/20089/25/20089/25/2008 2:35:49 PMPFAIL
The required module for the chippery has not been installed yet. Nobody was on site.
FIR08-00592 INSP-Final Inspection9/25/20089/25/20089/25/2008 1:26:59 PMPPASS
Permit finaled
BLD07-02106 FIRE-Final Inspection9/24/20089/25/20089/25/2008 1:26:31 PMAPASS
Life safety passed
BLD08-00952 FIRE-Final Inspection9/24/20089/25/20089/25/2008 11:24:55 AMAPASS
Life safety passed.
FIR08-00551 INSP-Sprinkler Rough-in9/24/20089/25/20089/25/2008 11:24:01 AMAPART
All of the outstanding rough-in issues have been taken care of except for verification from Tyco that the BB1 head installation still meets the manufacturers listing at the two areas of roof transitions. I have approved cover for all areas except for these two locations. Forrest France first addressed this issue on 9-22-2008. I let Ryan know that approved resubmittals will be required prior to a final inspection. My "redlined" city approved drawings are to be submitted to Bryan Johnson with this resubmittal. The building owner was witness to and part of the above conversations. I also found one pendant head in the west wing that was overspaced. Correct spacing will be verified at the final.
BLD08-01056 FIRE-Alarm Testing9/23/20089/25/20089/25/2008 8:51:17 AMAFAIL
Ansul and fire alarm test on the chippery kiosk was failed due to a module no being installed yet. Per the contractor the module will be installed tonight and the inspection called back in for tomorrow.