Inspections for the day of: Friday, September 25, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC07-00871 Aging Inspection9/25/20099/25/20099/28/2009 9:29:55 AM CANC
ELE09-01152 Electrical Rough-In9/25/20099/25/20099/25/2009 3:09:03 PMPPASS
underground for pole lights Phone #: ###-#### Internet Inspection Request from: Ron Zimmerman ok
ELE09-00783 Electrical Rough-In9/25/20099/25/20099/25/2009 3:08:43 PMPPASS
Danny-ceiling inspection please Phone #: ###-#### mens rest rm and deli ceilings ok
ELE09-01827 Electrical Rough-In9/25/20099/25/20099/25/2009 2:23:38 PMPPASS
troy Phone #: ###-#### ok
ELE09-01831 Electrical Rough-In9/25/20099/25/20099/25/2009 1:46:34 PMPPASS
Jimmy Phone #: ###-####ok
ELE09-01594 Electrical Rough-In9/25/20099/25/20099/25/2009 1:29:45 PMPPASS
Electrician on site - Gene. Please do Common area and gear rough-in only. Thank you! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson see added r/i p/s
ELE09-01594 Rough-In Permanent Service9/25/20099/25/20099/25/2009 1:29:15 PMPPASS
Electrician on site - Gene. Please do Common area and gear rough-in only. Thank you! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i all common areas ok p/s u/g new ok
ELE09-01830 Permanent Service9/25/20099/25/20099/25/2009 12:23:05 PMPPASS
Tom Phone #: ###-#### p/s u/g rec. ok
ELE09-01830 Final9/25/20099/25/20099/25/2009 12:21:50 PMPPASS
Tom Phone #: ###-#### ok
ELE09-01210 Final9/24/20099/25/20099/25/2009 11:44:25 AMAPASS
Please provide final inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok card signed
ELE09-01207 Final9/24/20099/25/20099/25/2009 11:44:06 AMAPASS
Please provide final inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok card signed
ELE09-01337 Final9/24/20099/25/20099/25/2009 10:39:00 AMAPASS
Front door will be open. Phone #: ###-#### Internet Inspection Request from: Joe Thomas
ELE07-02961 Electrical Rough-In9/24/20099/25/20099/25/2009 10:04:24 AMAFAIL
john Phone #: ###-#### met owner corr. 410.2&16 clearence for closet fixtures, 210.52(A) outlet spacing, fixed panel of sider, recepts not allowed above baseboard heaters, 210.52(F)&210.11(C)(2)all recept outlets in laundry rm shall be 20 amp laundry circuit, 314,16 box fill everywhere 314.43 screws not alled in non-metallic boxes, 300.14 shall provide 6" free length conductor note some of the violations posted are the same ones noted on prior inspection back in 2008
ELE09-01556 Final9/24/20099/25/20099/25/2009 9:56:08 AMAPASS
Please call Jeff Creek at ####-#### w/ 1/2 notice for access. Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek survey needs gfci for recepts within 6ft of laundry sink, talked with ele contr he will correct
ELE09-01824 Final9/24/20099/25/20099/25/2009 8:34:13 AMAFAIL
call Stan for access ###-#### Phone #: ###-#### Internet Inspection Request from: Bruce Herold corr called clean t/s 110.12(B)
110.3(B) feeder to job trailer shall be sized to trailer nameplate, T400.5(A) size co cord for amps, provide access to site, call for a t/s inspection 110.9&10 gear shall be rated for fault and short circuit currentwhen next to xformer