Inspections for the day of: Tuesday, September 25, 2012.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00588 ELE-Aging Inspection9/25/20129/25/201210/2/2012 3:10:08 PM DONE
Called and left massage with electrical contractor
ELE11-01314 ELE-Aging Inspection9/25/20129/25/20129/25/2012 2:31:10 PM PASS
Final ok
GCE12-00139 GCE-Final9/24/20129/25/20129/25/2012 1:49:54 PMAPASS
Terry @ ###-####
Final for Hot Tub
AM Inspection Final ok
GCE12-00120 GCE-Final9/24/20129/25/20129/25/2012 1:49:02 PMAPASS
Terry @ ###-####
AM Inspection Final ok
ELE11-02301 Final9/24/20129/25/20129/25/2012 1:20:20 PMAPASS
Call ahead for access - Steven Phone #: ###-#### Final ok
ELE12-02200 Permanent Service9/25/20129/25/20129/25/2012 12:53:27 PMPNR
Phone #: ###-#### >> Inspection requested via web by Patrick Paz will call when ready
ELE12-01698 Rough-In Permanent Service9/25/20129/25/20129/25/2012 12:40:00 PMPPASS
New service inspection. Contact on job is Jake Giese. Phone #: ###-#### >> Inspection requested via web by Richard Montgomery p/s ug n ok
ELE12-02385 Electrical Rough-In9/24/20129/25/20129/25/2012 10:42:29 AMAPASS
Phone #: ###-#### >> Inspection requested via web by joel smith addition rough cover ok
ELE12-01638 Electrical Rough-In9/24/20129/25/20129/25/2012 10:10:06 AMAPASS
Steve. Service meat department. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Meat fish ceiling ok cover
ELE12-02318 Electrical Rough-In9/24/20129/25/20129/25/2012 9:34:42 AMAFAIL
THANK YOU , BILL Phone #: ###-#### >> Inspection requested via web by Bob Glenn Called NEC320.23A NMB with-in 6' of attic access shall be protected from physical damage. NEC 334-17 NMB running through framing member shall be protected from physical damage where bored hole that are not 1 1/4" back from face of stud.
NEC 334.30 Securing and supporting- NMB stapled on 2x4 studs shall be supported 1 1/4" back from stud face.
BCC- One shall provide safe work space. Hand railing upstairs.
Change electrical permit to include 2nd AC, hot tub, and 14 rooms
ELE12-01545 Final9/24/20129/25/20129/24/2012 12:46:02 PMACANC
>> Inspection requested via web by Stephanie White Inspection cancelled from web by: Stephanie White