Inspections for the day of: Wednesday, September 25, 2013.
Number of inspections: 8
Percentage of inspections complete: 88 %
Percentage of inspections not complete: 13 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-02286 FIRE-Conference9/23/20139/23/2013 P 
Matt phone #: ###-####
FIR13-00170 INSP-Final Inspection9/24/20139/25/20139/26/2013 7:18:09 AMPFAIL
Gatehouse system inspection items inlcude; provde H/S at the workshop, SD at the 1st floor office needs relocated away from the HVAC diffuser, change descriptor at the 2nd floor SD storage room, alarm verification feature appears to be enabled for system smokes, panel map needs to include initiating device locations per review note #26, provide knox box per review comment #27, need FD approval for the toggle switch at the main panel MP. HD not tested at this time. Notification appliances and manual pull stations tested okay.
BLD13-02209 FIRE-Final Inspection9/24/20139/25/20139/25/2013 2:58:38 PMPFAIL
Missing approved plans, review comments, permit documents on site. Provide directional indicator at the second exit sign, a fire alarm permit may be required for new cooking appliances.
BLD13-01882 FIRE-Final Inspection9/24/20139/25/20139/25/2013 2:54:37 PMPPASS
Remainder of correction items field verified for completion. Fire life safety final approved.
BLD13-01020 FIRE-Final Inspection9/24/20139/25/20139/25/2013 1:30:05 PMAPART
Noted correction items at the retail store portion of this permit work passed reinspection. New fuel islands are not yet constructed.
FIR13-00398 INSP-Final Inspection9/24/20139/25/20139/25/2013 1:26:28 PMAPASS
Fire alarm work passed inspection. Permit final approved.
FIR13-00394 INSP-Final Inspection9/24/20139/25/20139/25/2013 1:25:03 PMAPASS
Scope of work finished. Functional testing passed. Fire alarm permit finaled.
BLD13-02496 FIRE-Final Inspection9/24/20139/25/20139/25/2013 1:15:35 PMAPASS
Fire life safety passed.