FIR13-00095
| INSP-Final Inspection | 9/24/2013 | 9/25/2013 | 9/25/2013 3:42:25 PM | P | PASS |
|
|
Permit finaled
|
BLD12-00811
| FIRE-Final Inspection | 9/25/2013 | 9/25/2013 | 9/25/2013 2:27:38 PM | P | FAIL |
|
|
Provide single action hardware on the pump room doors and provide annual inspections for all of the fire extinguishers. Front door meets requirements for locking hardware though panic is shown. The rear combustible ramp is under 4' in width so it meets the non-sprinkler exception. Exit signs and emergency lights functioned correctly.
|
FIR13-00502
| INSP-Sprinkler Rough-in | 9/25/2013 | 9/25/2013 | 9/25/2013 2:24:48 PM | P | PASS |
|
|
Rough-in passed and sprinkler piping can be covered. There is one problem with a head blocked at a column. It does not meet the 4 times rule for sprinkler obstructions to extended coverage heads. This will need to be corrected and will be verified at the final.
|
FIR13-00115
| INSP-Final Inspection | 9/24/2013 | 9/25/2013 | 9/25/2013 2:14:39 PM | A | PASS |
|
|
Permit finaled
|
BLD13-02175
| FIRE-Final Inspection | 9/24/2013 | 9/25/2013 | 9/25/2013 9:20:59 AM | A | PASS |
|
|
life safety passed
|
FIR13-00343
| INSP-Sprinkler Rough-in | 9/24/2013 | 9/25/2013 | 9/25/2013 9:18:31 AM | A | FAIL |
|
|
No inspection performed due to the pipe routing not matching the approved plans. Contractor shall contact the plan reviewer to verify if plan modifications are required due to changed hydraulic calculations or if as-builts can be acceptable.
|