GCE14-00152
| GCE-Rough-In | 9/18/2014 | 9/18/2014 | | P | |
|
|
HP ###-#### underground
|
ELE14-02678
| Final | 9/25/2014 | 9/25/2014 | 9/25/2014 4:32:25 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Don Conley electrical contractors work ok but mechanical contractor ran 220 volt for mini splits. NM cable not rated for exterior to heat pump
|
ELE14-02527
| Rough-In Permanent Service | 9/25/2014 | 9/25/2014 | 9/25/2014 3:52:23 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov unit 101,102,201 and 202 r/i ok p/s u/g n ok 4 units and house panel
|
ELE14-01652
| Electrical Rough-In | 9/25/2014 | 9/25/2014 | 9/25/2014 2:49:28 PM | P | PASS |
|
|
Josh-solar Phone #: ###-#### r/i and final for solar ok
|
ELE14-02518
| Permanent Service | 9/25/2014 | 9/25/2014 | 9/25/2014 2:26:14 PM | P | PASS |
|
|
This is for a service change inspection. Please call ###-#### before inspection Phone #: ###-#### Inspection requested via web by Emmet Bushman p/s u/g rec ok
|
ELE14-01482
| Final | 9/25/2014 | 9/25/2014 | 9/25/2014 1:51:24 PM | P | PASS |
|
|
Please give me half an hour notice to insure access Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman final ok
|
ELE14-01006
| Final | 9/25/2014 | 9/25/2014 | 9/25/2014 1:33:16 PM | P | PASS |
|
|
Please give me half an hour notice to insure access Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman final ok
|
ELE14-02482
| Electrical Rough-In | 9/25/2014 | 9/25/2014 | 9/25/2014 12:56:14 PM | P | CANC |
|
|
remodel of garage and house Phone #: ###-#### Inspection requested via web by Darryn Coburn called in twice
|
ELE14-02482
| Electrical Rough-In | 9/25/2014 | 9/25/2014 | 9/25/2014 12:55:50 PM | P | NR |
|
|
remodel of garage and house Phone #: ###-#### Inspection requested via web by Darryn Coburn no access to house. garage loadcenter requires separate grounding electrode. still need underground inspection for subfeed.
|
ELE14-02670
| Final | 9/25/2014 | 9/25/2014 | 9/25/2014 12:29:00 PM | A | PASS |
|
|
wire ac Phone #: ###-#### Inspection requested via web by PAT MILLER final ok
|
ELE14-02670
| Electrical Rough-In | 9/25/2014 | 9/25/2014 | 9/25/2014 12:27:43 PM | A | PASS |
|
|
wire ac Phone #: ###-#### Inspection requested via web by PAT MILLER r/i ok
|
ELE14-01891
| Electrical Rough-In | 9/25/2014 | 9/25/2014 | 9/25/2014 12:09:26 PM | P | PASS |
|
|
Need inspection to cover heat mat in master bath room. Phone #: ###-#### Inspection requested via web by Alan Lusk r/i floor heat ok
|
ELE14-02302
| Electrical Rough-In | 9/24/2014 | 9/25/2014 | 9/25/2014 11:35:08 AM | A | PASS |
|
|
Swimming pool light potting compound Phone #: ###-#### Inspection requested via web by Lars Johnson r/i ok
|
ELE14-02062
| Rough-In Permanent Service | 9/24/2014 | 9/25/2014 | 9/25/2014 11:17:38 AM | A | FAIL |
|
|
Mucho Phone #: ###-#### 110.26(A)(2)- Width of working space needs to be 30 inches minimum around meter base. 250.52(A)(3)(2) A concrete encased electrode consist of at least 20 foot of steel in direct contact with earth. stemwall not acceptable (see info note). 3 inch secondary from ID.Power too croocked for locknut and terminal connector to be installed properly. Suggest bringing meter base out until 3 inch conduit is straight.
|
ELE14-02062
| Electrical Rough-In | 9/25/2014 | 9/25/2014 | 9/25/2014 11:11:18 AM | P | PASS |
|
|
Mucho Phone #: ###-#### r/i ok can light in soffit needs 2 hr encapsulation
|
ELE14-01182
| Electrical Rough-In | 9/24/2014 | 9/25/2014 | 9/25/2014 10:10:00 AM | A | PASS |
|
|
Please call Shane prior to inspection at ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 3rd floor so. west office chase r/i ok
|
ELE14-02666
| Electrical Rough-In | 9/24/2014 | 9/25/2014 | 9/25/2014 9:57:07 AM | A | PASS |
|
|
We are requesting a wall rough-in inspection for tomorrow morning in the AM. Our onsite contact is Rod Thomlinson @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate r/i walls ok
|
ELE14-02638
| Final | 9/24/2014 | 9/25/2014 | 9/25/2014 9:29:40 AM | A | PASS |
|
|
Inspection requested via web by HZ ZAHIC final ok
|
ELE14-02632
| Final | 9/24/2014 | 9/25/2014 | 9/25/2014 9:10:04 AM | A | PASS |
|
|
Brent Phone #: ###-#### final ok
|
ELE14-02632
| Permanent Service | 9/25/2014 | 9/25/2014 | 9/25/2014 9:08:50 AM | P | PASS |
|
|
Brent Phone #: ###-#### p/s o/h rec ok
|
ELE14-02161
| Final | 9/25/2014 | 9/25/2014 | 9/25/2014 8:49:55 AM | A | PASS |
|
|
call for access Phone #: ###-#### Inspection requested via web by PAT MILLER final ok
|
ELE12-01907
| ELE-Aging Inspection | 9/25/2014 | 9/25/2014 | 9/25/2014 7:51:04 AM | | DONE |
|
|
too busy
|
ELE12-01914
| ELE-Aging Inspection | 9/25/2014 | 9/25/2014 | 9/25/2014 7:50:40 AM | | DONE |
|
|
too busy
|
ELE12-03112
| ELE-Aging Inspection | 9/25/2014 | 9/25/2014 | 9/25/2014 7:50:18 AM | | DONE |
|
|
too busy
|