Inspections for the day of: Thursday, September 25, 2014.
Number of inspections: 24
Percentage of inspections complete: 96 %
Percentage of inspections not complete: 4 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCE14-00152 GCE-Rough-In9/18/20149/18/2014 P 
HP ###-#### underground
ELE14-02678 Final9/25/20149/25/20149/25/2014 4:32:25 PMPFAIL
Phone #: ###-#### Inspection requested via web by Don Conley electrical contractors work ok but mechanical contractor ran 220 volt for mini splits. NM cable not rated for exterior to heat pump
ELE14-02527 Rough-In Permanent Service9/25/20149/25/20149/25/2014 3:52:23 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov unit 101,102,201 and 202 r/i ok p/s u/g n ok 4 units and house panel
ELE14-01652 Electrical Rough-In9/25/20149/25/20149/25/2014 2:49:28 PMPPASS
Josh-solar Phone #: ###-#### r/i and final for solar ok
ELE14-02518 Permanent Service9/25/20149/25/20149/25/2014 2:26:14 PMPPASS
This is for a service change inspection. Please call ###-#### before inspection Phone #: ###-#### Inspection requested via web by Emmet Bushman p/s u/g rec ok
ELE14-01482 Final9/25/20149/25/20149/25/2014 1:51:24 PMPPASS
Please give me half an hour notice to insure access Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman final ok
ELE14-01006 Final9/25/20149/25/20149/25/2014 1:33:16 PMPPASS
Please give me half an hour notice to insure access Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman final ok
ELE14-02482 Electrical Rough-In9/25/20149/25/20149/25/2014 12:56:14 PMPCANC
remodel of garage and house Phone #: ###-#### Inspection requested via web by Darryn Coburn called in twice
ELE14-02482 Electrical Rough-In9/25/20149/25/20149/25/2014 12:55:50 PMPNR
remodel of garage and house Phone #: ###-#### Inspection requested via web by Darryn Coburn no access to house. garage loadcenter requires separate grounding electrode. still need underground inspection for subfeed.
ELE14-02670 Final9/25/20149/25/20149/25/2014 12:29:00 PMAPASS
wire ac Phone #: ###-#### Inspection requested via web by PAT MILLER final ok
ELE14-02670 Electrical Rough-In9/25/20149/25/20149/25/2014 12:27:43 PMAPASS
wire ac Phone #: ###-#### Inspection requested via web by PAT MILLER r/i ok
ELE14-01891 Electrical Rough-In9/25/20149/25/20149/25/2014 12:09:26 PMPPASS
Need inspection to cover heat mat in master bath room. Phone #: ###-#### Inspection requested via web by Alan Lusk r/i floor heat ok
ELE14-02302 Electrical Rough-In9/24/20149/25/20149/25/2014 11:35:08 AMAPASS
Swimming pool light potting compound Phone #: ###-#### Inspection requested via web by Lars Johnson r/i ok
ELE14-02062 Rough-In Permanent Service9/24/20149/25/20149/25/2014 11:17:38 AMAFAIL
Mucho Phone #: ###-#### 110.26(A)(2)- Width of working space needs to be 30 inches minimum around meter base. 250.52(A)(3)(2) A concrete encased electrode consist of at least 20 foot of steel in direct contact with earth. stemwall not acceptable (see info note). 3 inch secondary from ID.Power too croocked for locknut and terminal connector to be installed properly. Suggest bringing meter base out until 3 inch conduit is straight.
ELE14-02062 Electrical Rough-In9/25/20149/25/20149/25/2014 11:11:18 AMPPASS
Mucho Phone #: ###-#### r/i ok can light in soffit needs 2 hr encapsulation
ELE14-01182 Electrical Rough-In9/24/20149/25/20149/25/2014 10:10:00 AMAPASS
Please call Shane prior to inspection at ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 3rd floor so. west office chase r/i ok
ELE14-02666 Electrical Rough-In9/24/20149/25/20149/25/2014 9:57:07 AMAPASS
We are requesting a wall rough-in inspection for tomorrow morning in the AM. Our onsite contact is Rod Thomlinson @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate r/i walls ok
ELE14-02638 Final9/24/20149/25/20149/25/2014 9:29:40 AMAPASS
Inspection requested via web by HZ ZAHIC final ok
ELE14-02632 Final9/24/20149/25/20149/25/2014 9:10:04 AMAPASS
Brent Phone #: ###-#### final ok
ELE14-02632 Permanent Service9/25/20149/25/20149/25/2014 9:08:50 AMPPASS
Brent Phone #: ###-#### p/s o/h rec ok
ELE14-02161 Final9/25/20149/25/20149/25/2014 8:49:55 AMAPASS
call for access Phone #: ###-#### Inspection requested via web by PAT MILLER final ok
ELE12-01907 ELE-Aging Inspection9/25/20149/25/20149/25/2014 7:51:04 AM DONE
too busy
ELE12-01914 ELE-Aging Inspection9/25/20149/25/20149/25/2014 7:50:40 AM DONE
too busy
ELE12-03112 ELE-Aging Inspection9/25/20149/25/20149/25/2014 7:50:18 AM DONE
too busy