Inspections for the day of: Monday, September 25, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00275 INSP-Sprinkler Rough-in/Hydro9/25/20179/25/20179/25/2017 2:41:40 PMPPASS
UG hydro passed
NAF17-00037 INSP-Final9/25/20179/25/20179/25/2017 2:40:50 PMPCANC
Not ready yet per electrician. Need the smoke alarms connected to the flow switch per review note #2.

Call for access Phone #: 2085504599 >> Inspection requested via mobile web by Stevie Ray
FIR17-00146 INSP-Sprinkler Rough-in9/22/20179/25/20179/25/2017 1:30:24 PMPFAIL
Plan modifications are required due to the south main being relocated. Earth quake bracing is missing and when install not located as shown on the prints. Branchline siesmic restraints are missing and where installed are "bowed" and will not work during compression. The remote FDC has been buried in a wall with no inspection. No real inspection was performed due to the need for the plan modifications so Charles and I did a conference. Job is nearly ready for cover and this is the first rough-in inspection called for.
FIR09-00051 FIR-Aging Inspection9/25/20179/25/20179/25/2017 10:03:46 AM NR
contractor is out of business
FIR08-00550 FIR-Aging Inspection9/25/20179/25/20179/25/2017 10:01:53 AM NR
Waiting for fire dept. follow up and contractor to call for final inspection
BLD17-01815 FIRE-Final Inspection9/22/20179/25/20179/25/2017 9:52:06 AMAPASS
Life safety passed
BLD17-02310 FIRE-Final Inspection9/22/20179/25/20179/25/2017 9:28:54 AMAPASS
life safety passed

Gil Phone #: ###-####
NAF17-00041 INSP-Final9/22/20179/25/20179/25/2017 8:37:31 AMACANC
After ten am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
NAF17-00052 INSP-Final9/22/20179/25/20179/25/2017 8:36:34 AMACANC
After ten am Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
BLD16-04365 FIRE-Final Inspection9/22/20179/25/20179/25/2017 8:04:08 AMAPASS
Life safety passed.

Joe Phone #: ###-####