ELE18-02777
| Final | 9/25/2018 | 9/25/2018 | 9/25/2018 3:52:05 PM | P | PART |
|
|
TCO for bar and sitting area ###-#### Chris. South east side of bar unable to provide GFCI protection for receptacles located on back side for mobile devices and 1 inside bar receptacle due to wiring method used. If unable to GFCI area needed these circuits shall be locked out until compliant with NEC. Bar needs to open evening of 9-25-18. Contractor agrees to complete or lock out. TCO ok
|
ELE18-03676
| Permanent Service | 9/24/2018 | 9/25/2018 | 9/25/2018 2:29:23 PM | P | PASS |
|
|
Meter Inspection Any questions call Jack Phone #: ###-#### Inspection requested via web by Jack Bernard Service off for more than a year. Reconnect and all labelled. p/s u/g rec ok
|
ELE18-03676
| Final | 9/25/2018 | 9/25/2018 | 9/25/2018 2:27:48 PM | P | PASS |
|
|
Meter Inspection Any questions call Jack Phone #: ###-#### Inspection requested via web by Jack Bernard Final ok
|
ELE18-02214
| Electrical Rough-In | 9/25/2018 | 9/25/2018 | 9/25/2018 2:27:07 PM | P | PASS |
|
|
Ceiling grid for cover Phone #: ###-#### Inspection requested via web by kendall bender Grid rough in ok cover
|
ELE18-02777
| Final | 9/25/2018 | 9/25/2018 | 9/25/2018 1:26:51 PM | P | FAIL |
|
|
Partial final bar area please call Chris 9411710 prior to inspection Phone #: ###-#### Inspection requested via web by Ryan Wake 210.8- All 20 amp 120 volt receptacle outlets located within 6' of a sink shall have GFCI protection. GFCI devices shall be installed in a readily accessible location. Receptacles behind appliances and on back side of bar for charging mobile devices.
|
ELE18-02064
| Final | 9/24/2018 | 9/25/2018 | 9/25/2018 12:23:02 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez 110.3- Devices not working, dead reeptacles in dining room, family room, up master bedroom, open neutral in family room. 300.22(B)- Electrical wiring and devices shall not be located in a duct. NM cable and non-metellic box located in area used as return air space under stairs. 406.6- Missing receptacle cover in master bedroom behind closet door. 410.16- Recessed can trims in master closet shall have totally enclosed lamps.
|