Inspections for the day of: Tuesday, September 25, 2018.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02777 Final9/25/20189/25/20189/25/2018 3:52:05 PMPPART
TCO for bar and sitting area ###-#### Chris.
South east side of bar unable to provide GFCI protection for receptacles located on back side for mobile devices and 1 inside bar receptacle due to wiring method used. If unable to GFCI area needed these circuits shall be locked out until compliant with NEC. Bar needs to open evening of 9-25-18. Contractor agrees to complete or lock out. TCO ok
ELE18-03676 Permanent Service9/24/20189/25/20189/25/2018 2:29:23 PMPPASS
Meter Inspection Any questions call Jack Phone #: ###-#### Inspection requested via web by Jack Bernard
Service off for more than a year. Reconnect and all labelled. p/s u/g rec ok
ELE18-03676 Final9/25/20189/25/20189/25/2018 2:27:48 PMPPASS
Meter Inspection Any questions call Jack Phone #: ###-#### Inspection requested via web by Jack Bernard Final ok
ELE18-02214 Electrical Rough-In9/25/20189/25/20189/25/2018 2:27:07 PMPPASS
Ceiling grid for cover Phone #: ###-#### Inspection requested via web by kendall bender
Grid rough in ok cover
ELE18-02777 Final9/25/20189/25/20189/25/2018 1:26:51 PMPFAIL
Partial final bar area please call Chris 9411710 prior to inspection Phone #: ###-#### Inspection requested via web by Ryan Wake
210.8- All 20 amp 120 volt receptacle outlets located within 6' of a sink shall have GFCI protection. GFCI devices shall be installed in a readily accessible location. Receptacles behind appliances and on back side of bar for charging mobile devices.
ELE18-02064 Final9/24/20189/25/20189/25/2018 12:23:02 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kevin Perez
110.3- Devices not working, dead reeptacles in dining room, family room, up master bedroom, open neutral in family room.
300.22(B)- Electrical wiring and devices shall not be located in a duct. NM cable and non-metellic box located in area used as return air space under stairs.
406.6- Missing receptacle cover in master bedroom behind closet door.
410.16- Recessed can trims in master closet shall have totally enclosed lamps.