Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02888 Final9/25/20199/25/20199/25/2019 2:53:38 PMPPASS
Call Scott for access, he will meet you on the corner of Capital ; Front St.
If you cannot get a hold of Scott, please call Mike @ ###-#### and he will get you in to complete inspection. Thank you! Phone #: ###-#### Inspection requested via web by Bonnie Page
Final ok
ELE19-00558 Permanent Service9/25/20199/25/20199/25/2019 2:29:31 PMPPASS
Please call when in route Phone #: ###-#### Inspection requested via web by Spencer McLean
p/s u/g n ok
ELE19-00602 Electrical Rough-In9/25/20199/25/20199/25/2019 2:28:31 PMPPASS
Shear wall cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Shear wall level 2 south east corner rough in ok cover
ELE19-02900 Final9/24/20199/25/20199/25/2019 11:06:22 AMANH
Joel Hopkins is contact ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Contact provided on site contact of Carl MIller at 208-250- 6923 who I tried to call on arrival. Unable to reach contact provided, was not offered a chance to leave message. Due to work load not able to sit and wait for others to arrive. Recal when someone available for access.
ELE19-02966 Rough-In Permanent Service9/24/20199/25/20199/25/2019 10:36:52 AMAPASS
Phone #: ###-#### Inspection requested via web by Icon Electric
Rough in ok cover p/s u/g n ok
ELE19-03630 Temporary Service9/24/20199/25/20199/25/2019 10:16:32 AMAPASS
Phone #: ###-#### Inspection requested via web by danny perrine t/s o/h n ok
ELE19-01640 Final9/24/20199/25/20199/25/2019 9:46:13 AMAPASS
garage code 0813 Phone #: ###-#### Inspection requested via web by cal crosby
Final ok
ELE19-03596 Rough-In Permanent Service9/24/20199/25/20199/25/2019 9:14:52 AMAFAIL
Phone #: ###-#### Inspection requested via web by Dean Gernaat
110.3- Fan/ light combo shown on print for master shower listing shall be verified.
250.68- Connection to concrete encased electode shall remain accessible. mud ring missing.
300.4- Wher NM cable passes thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage. Master bath near shower.
334.30- NM supports shall not exceed 4 1/2'. Garage tall bay.
424.28- Over current protection for furnace shall be 20 amp as per nameplate. 15 amp installed