Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03422 ELE-Aging Inspection9/25/20199/25/20199/26/2019 2:44:14 PM PASS
under construction
ELE19-03639 Electrical Rough-In9/25/20199/25/20199/25/2019 2:42:53 PMPPASS
Later this afternoon please. Underslab for kitchen islands. Phone #: ###-#### Inspection requested via web by Todd Hall...ok to cover ...BLDG B
ELE19-03385 Electrical Rough-In9/25/20199/25/20199/25/2019 2:14:23 PMPPASS
McGuire Phone #: ###-####704...
UL lised equipment verified
voltage/amperage rating label needed for final
breaker installed in panel...no access required for final
ELE19-03553 Electrical Rough-In9/25/20199/25/20199/25/2019 1:33:58 PMPPASS
call for access- Cory Phone #: ###-####...
outlets and needed switching/lighting wired with romex...will be covered and protected from physical damage...ok to cover
ELE19-03553 Conference9/25/20199/25/20199/25/2019 1:32:19 PMPPASS
Call for access- Cory Phone #: ###-####...
discussed back addition off garage...homeowner competent
ELE19-03442 Final9/25/20199/25/20199/25/2019 12:24:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Conley...ok to final
ELE19-03329 Final9/25/20199/25/20199/25/2019 11:59:45 AMPPASS
Chad Vanorden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce...ok to final ..card signed
ELE19-03564 Final9/24/20199/25/20199/25/2019 11:29:12 AMPPASS
Phone #: ###-#### Inspection requested via web by Joseph Yergensen...
labelling, disconnect, and OCPD ok
ELE19-03564 Electrical Rough-In9/24/20199/25/20199/25/2019 11:27:51 AMAPASS
I will be on site with both Electrical and Building permits, Thank You! Phone #: ###-#### Inspection requested via web by Joseph Yergensen...UL listed equipment verified
ELE19-02774 Electrical Rough-In9/24/20199/25/20199/25/2019 10:53:32 AMAPASS
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden...
walls and bathroom hardlids ok to cover
ELE19-02773 Electrical Rough-In9/24/20199/25/20199/25/2019 10:35:36 AMAPASS
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden...
walls and bath hard lids ok to cover
ELE18-04054 Permanent Service9/24/20199/25/20199/25/2019 10:29:37 AMAPASS
Contact: Mike Mulvahill, service inspection for main service and house panel please Phone #: ###-#### Inspection requested via web by Deb Gooden...p/s u/g new ok
ELE19-03629 Permanent Service9/24/20199/25/20199/25/2019 10:17:15 AMAFAIL
please call 30mins ahead- Jeremy Phone #: ###-####...
1) seperate building requires disconnect on exteriorof building
2) buildings meter location needs verified and labelled
ELE19-02554 Final9/24/20199/25/20199/25/2019 9:34:53 AMAFAIL
Please call ###-#### to ensure access. Phone #: ###-#### Inspection requested via web by William Salts...
1) outside outlet at panel shall be W/R rated
2) panel shall be completely labelled
3) 2ft of wall space shall have an outlet
4) junction box cover needs installed
5) requiring manufacters information on feed thru bridge in panel
ELE19-03363 Electrical Rough-In9/21/20199/25/20199/25/2019 8:54:19 AMAFAIL
Crew Lead is Justin. Crew will be there to install solar panels in the morning. Office line is ###-####. Phone #: ###-#### Inspection requested via web by Amy Simms....
no one onsite...no material on site......no answer on contacts phone
ELE19-03289 Final9/24/20199/25/20199/25/2019 8:26:55 AMANR
Phone #: ###-#### Inspection requested via web by Thomas wilson....meter required for final
ELE19-03151 Final9/24/20199/25/20199/25/2019 8:26:31 AMANR
Phone #: ###-#### Inspection requested via web by Thomas wilson...meter required for final
ELE19-03457 Final9/24/20199/25/20199/25/2019 8:26:07 AMANR
Phone #: ###-#### Inspection requested via web by Thomas wilson....meter required for final
ELE19-03387 Final9/24/20199/25/20199/25/2019 8:25:41 AMANR
Phone #: ###-#### Inspection requested via web by Thomas wilson...meter required for final
ELE19-03386 Final9/24/20199/25/20199/25/2019 8:25:16 AMANR
Phone #: ###-#### Inspection requested via web by Thomas wilson...meter required for final
ELE19-03026 Final9/24/20199/25/20199/25/2019 8:21:23 AMANR
Phone #: ###-#### Inspection requested via web by Thomas wilson...meter required for final
ELE19-03458 Final9/24/20199/25/20199/25/2019 8:20:55 AMANR
Phone #: ###-#### Inspection requested via web by Thomas wilson..meter required for final
ELE17-03395 ELE-Aging Inspection9/25/20199/25/20199/25/2019 7:39:45 AM PASS
finaled...see notes
ELE17-03395 Final9/25/20199/25/20199/25/2019 7:39:23 AMPPASS
previously finaled ...cancelled by accident...se notes
ELE17-03346 DOC - Permit Expired9/25/20199/25/20199/25/2019 7:37:13 AMAPASS
no work on permit for 180 days...permit expired
ELE17-03306 Final9/25/20199/25/20199/25/2019 7:23:35 AMAPASS
was for trench only
no other work under permit
ELE19-03494 Electrical Rough-In9/25/20199/25/20199/25/2019 7:05:32 AMACANC
On site. Phone #: ###-#### >> Inspection requested via web by Garrett Collins Inspection cancelled from web by: Garrett Collins