ELE01-02065
| ELE-Aging Inspection | 9/26/2001 | 9/26/2001 | 9/26/2001 12:00:00 AM | | NR |
|
|
contractor to call for inspection 10/3/2001 8:47:57 AM
|
ELE01-02827
| Permanent Service | 9/25/2001 | 9/26/2001 | 9/26/2001 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 09/25/2001 at 12:49:23. Contact: ###-####. ok cover cover concrete ufer ground 9/26/2001 9:55:29 AM
|
ELE01-03033
| Final | 9/25/2001 | 9/26/2001 | 9/26/2001 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 09/25/2001 at 16:40:16. Contact: ###-####. ok final 9/26/2001 10:12:00 AM
|
ELE01-00146
| Electrical Rough-In | 9/25/2001 | 9/26/2001 | 9/26/2001 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 09/25/2001 at 19:03:22. Contact: ###-####. ok cover ceilings corridors 1st level areas 3,4,5,6,7,&8 9/26/2001 9:45:27 AM
|
ELE01-03097
| Final | 9/25/2001 | 9/26/2001 | 9/26/2001 12:00:00 AM | P | NR |
|
|
###-#### john called in wrong permit # 9/26/2001 3:10:43 PM
|
ELE01-03215
| Final | 9/25/2001 | 9/26/2001 | 9/26/2001 12:00:00 AM | P | PART |
|
|
fn ###-#### craig not ready conf with electrician regarding grounding 9/26/2001 2:14:31 PM
|
ELE01-03344
| Final | 9/26/2001 | 9/26/2001 | 9/26/2001 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 09/26/2001 at 09:40:18. Contact: ###-####. fail correction nec 110-3 shall use listed and labled equipment (flex jak connectors used for seal tight flex) called contractor 9/26/2001 12:58:40 PM 9/26/2001 12:58:59 PM
|
ELE01-03294
| Electrical Rough-In | 9/26/2001 | 9/26/2001 | 9/26/2001 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 412 On 9/26/2001 3:11:41 PM ok cover ufer ground with concrete
|