ELE03-01914
| ELE-Aging Inspection | 9/26/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | | PASS |
|
|
ok 9/26/2003 9:14:25 AM
|
ELE03-02723
| Electrical Rough-In | 9/25/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | A | PART |
|
|
pole lite bases --site work ###-####-- ok 9/26/2003 9:14:39 AM
|
ELE03-02728
| Final | 9/25/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | A | PASS |
|
|
detached gar is empty--rocky ###-#### ok 9/26/2003 8:17:37 AM
|
ELE03-03019
| Rough-In Permanent Service | 9/25/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas
r/i ok
p/s u/g new ok 9/26/2003 10:41:25 AM
|
ELE03-03020
| Permanent Service | 9/25/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | A | PASS |
|
|
PERMANENT SERVICE AND WE NEED TO GET POWER THERE ASAP. PLEASE CONTACT US SO WE CAN GET THE POWER SET UP AND ON WHEN YOU HAVE INSPECTED.
p/s o/h rec. ok 9/26/2003 8:37:14 AM
|
ELE03-02990
| Temporary Service | 9/25/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | A | FAIL |
|
|
Please call if any problems; Phone #: ###-#### Internet Inspection Request from: Gary Foreman called 110.12(C) clean t/s 9/26/2003 10:10:29 AM
|
ELE03-02458
| Electrical Rough-In | 9/25/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 9/25/2003 at 11:48:21 AM. Contact: ###-####. pool u/g ok 9/26/2003 9:45:54 AM
|
ELE03-02683
| Temporary Service | 9/25/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | P | CANC |
|
|
CONTACT TOM BETTY; Phone #: ###-#### Internet Inspection Request from: Deb McCoy needs PM# for t/s shall not use building electrical PM# 9/25/2003 12:44:39 PM
|
ELE03-03014
| Temporary Service | 9/26/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | P | PASS |
|
|
CONTACT: TOM BETTY
; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
t/s u/g new ok 9/26/2003 12:23:46 PM
|
ELE03-01474
| Final | 9/26/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | P | FAIL |
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 250.148 grd box at island, 406.4(D) recepts shall be flush with plates, 314.20 needs box extensions where boxes are set back more than 1/4" 210.52(A) outlet more than 6 ft left of bath entry in MBed, 300.5 uf too post light shall be 12" deep needs r/i inspection for trench, post address, need access to garage recepts doors in the way , install all light fixtures entry light 9/26/2003 4:09:34 PM
|
ELE03-02829
| Rough-In Permanent Service | 9/26/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | P | CANC |
|
|
daniel; Phone #: ###-#### Internet Inspection Request from: Darla Downs contractor called , he will will reschedule inspection when ready 9/26/2003 2:35:37 PM
|
ELE03-02576
| Final | 9/26/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | P | PASS |
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 9/26/2003 1:28:06 PM
|
ELE03-03025
| Conference | 9/26/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | P | PART |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 9/26/2003 2:34:55 PM
|
ELE03-03026
| Rough-In Permanent Service | 9/26/2003 | 9/26/2003 | 9/26/2003 12:00:00 AM | P | PART |
|
|
###-#### JOHN r/i ok only p/s not ready 9/26/2003 3:38:19 PM
|