Inspections for the day of: Friday, September 26, 2003.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00333 FIR-Aging Inspection9/26/20039/26/20039/26/2003 12:00:00 AM PASS
talked to George and the work is still in progress 9/26/2003 8:21:53 AM
FIR03-00412 INSP-Conference9/25/20039/26/20039/26/2003 12:00:00 AMAPART
8:00 met with Ernie, John, and Dan about fire alarm requirements and need for approval of plans and testing prior to occupancy; exit signs will need to be installed per plans; fire sprinklers are approved as stated in sprinkler review comments 9/26/2003 8:19:06 AM
FIR03-00503 INSP-Final Inspection9/25/20039/26/20039/26/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 9/25/2003 at 2:03:29 PM. Contact: ###-####.
FIR03-00481 INSP-Final Inspection9/25/20039/26/20039/26/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 9/25/2003 at 2:07:59 PM. Contact: ###-####.
FIR03-00104 INSP-Alarm Testing9/25/20039/26/20039/26/2003 12:00:00 AMAFAIL
smoke detectors need to be within 12 inches of deck in stairs and elevator machine room; need heat detectors added in elevator machine rooms; descriptor for first floor NAC detector and location has changed to update map also; need to test elevator recall and all flows and tampers; reverify phase reversal on fire pump; batteries not supervised; strobes in ADA sleeping rooms within 24 inches to be 177cd or lower strobe; need circuit breaker location on NAC's with lockout; tested location of devices on all living floors -okay; tested notification devices on all living floors - okay except ADA rooms; need updated maps and NFPA 72 forms when complete 9/26/2003 12:10:45 PM
BLD02-00090 FIRE-Final Inspection9/25/20039/26/20039/26/2003 12:00:00 AMAFAIL
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs 9/26/2003 12:11:47 PM smoke seal on all rated doors; need floor drain, emergency lights and heat in fire pump room; stair signage; sprinkler heads fire proofed in stairs and elevator machine room; fire extinguishers require current inspection tag; see alarm permit for other items 9/26/2003 12:14:47 PM
BLD03-01629 FIRE-Final Inspection9/26/20039/26/20039/26/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 9/26/2003 at 9:48:04 AM. Contact: ###-####.
FIR03-00565 INSP-Final Inspection9/26/20039/26/20039/26/2003 12:00:00 AMPFAIL
sam; Phone #: ###-#### Internet Inspection Request from: Darla Downs sprinkler system requires annual inspection; fire panel requires notification device; manual pull station and smoke detector above panel 9/26/2003 2:36:18 PM
FIR03-00512 INSP-Final Inspection9/26/20039/26/20039/26/2003 12:00:00 AMPPASS
FIR03-00331 INSP-Final Inspection9/26/20039/26/20039/26/2003 12:00:00 AMPPASS
FIR03-00095 INSP-Final Inspection9/24/20039/26/20039/26/2003 12:00:00 AMPPASS
###-#### don
FIR03-00096 INSP-Final Inspection9/24/20039/26/20039/26/2003 12:00:00 AMPPASS
###-#### don
FIR03-00097 INSP-Final Inspection9/24/20039/26/20039/26/2003 12:00:00 AMPPASS
###-#### don