Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00276 INSP-Final Inspection9/26/20039/26/20039/26/2003 9:36:06 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
FIR03-00267 INSP-Final Inspection9/26/20039/26/20039/26/2003 12:00:00 AMPFAIL
Phone #: ###-#### Monitoring company had the monitoring account messed up. No inspection could be performed. 9/26/2003 3:16:50 PM
BLD02-01073 FIRE-Final Inspection9/26/20039/26/20039/26/2003 12:00:00 AMPFAIL
fire alarm system could not be finaled. I went over door hardware and fire extinguisher issues with the superintendant for the project. 9/26/2003 3:18:29 PM
FIR03-00550 INSP-Conference9/26/20039/26/20039/26/2003 12:00:00 AMPDONE
I stopped by the project to verify if work had been done without permits. Work had indeed been performed without permits. According to Patrick, who was the installer of the fire alarm system, he pulled off the job the previous week. I talked to Barbara at the permit desk and had her double the permit fees as per policy. The contractor picked up the drawings shortly after. Dave Miller has instrucked me to cite the offending party.
BLD03-00094 FIRE-Final Inspection9/25/20039/26/20039/26/2003 12:00:00 AMPFAIL
provide one 2A,20BC fire extinguisher, provide sign for oxygen manifold per IFC2609.5, secure tanks per IFC 3003.3.3, provide shutoff valve signs per IFC 2609.3 and provide signage for tank contents. Preferrably NFPA 704 signs 9/26/2003 1:20:20 PM
FIR03-00216 INSP-Final Inspection9/26/20039/26/20039/26/2003 12:00:00 AMPFAIL
The monitoring company had the account messed up. No inspection performed 9/26/2003 3:19:11 PM