Inspections for the day of: Monday, September 26, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00064 INSP-Final Inspection9/21/20059/26/20059/26/2005 6:05:47 PMPPART
System tested okay, need to provide map at the panel and update the map with the new device addresses.
FIR05-00236 INSP-Final Inspection9/23/20059/26/20059/26/2005 3:55:52 PMAFAIL
SD is overspaced in file room, SD in two adjacent rooms as marked on plans are too close to HVAC diffusers, one strobe in restroom with drop ceiling is mounted too high, all other items tested okay, provide latest resubmittals at next inspection.
FIR05-00039 INSP-Supply line flush9/23/20059/26/20059/26/2005 1:23:26 PMPPART
Underground fire supply line flush is satisfactory, pitot reading measured 24 psi. at 4" opening under full flow condition.
MIS05-00158 FIR-Final9/26/20059/26/20059/26/2005 12:40:39 PMPCANC
kevin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Inspection rescheduled for tomorrow 9/27.
MIS05-00157 FIR-Final9/26/20059/26/20059/26/2005 12:39:28 PMPCANC
kevin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Inspection rescheduled for tomorrow 9/27
FIR05-00391 INSP-Final Inspection9/23/20059/26/20059/26/2005 11:30:58 AMACANC
Cancel inspection per Patrick at ###-####, the final location for HVAC diffusers is not complete thus affecting smoke detector location, Patrick to reschedule when ready.
FIR05-00429 INSP-Sprinkler Rough-in/Hydro9/23/20059/26/20059/26/2005 11:26:25 AMAPART
Overhead hydrostatic test passed inspection, main tie in is satisfactory, not all drops are cut in at this time.
BLD05-02289 FIRE-Final Inspection9/23/20059/26/20059/26/2005 10:10:51 AMAPASS
The provided fire extinguisher was relocated to a normal path of travel while on site, no fire sprinkler or alarm modifications were required, fire life safety passed inspection.
BLD04-01413 FIRE-Final Inspection9/26/20059/26/20059/26/2005 12:00:00 AMAPASS
Fire life safety finaled.