FIR05-00064
| INSP-Final Inspection | 9/21/2005 | 9/26/2005 | 9/26/2005 6:05:47 PM | P | PART |
|
|
System tested okay, need to provide map at the panel and update the map with the new device addresses.
|
FIR05-00236
| INSP-Final Inspection | 9/23/2005 | 9/26/2005 | 9/26/2005 3:55:52 PM | A | FAIL |
|
|
SD is overspaced in file room, SD in two adjacent rooms as marked on plans are too close to HVAC diffusers, one strobe in restroom with drop ceiling is mounted too high, all other items tested okay, provide latest resubmittals at next inspection.
|
FIR05-00039
| INSP-Supply line flush | 9/23/2005 | 9/26/2005 | 9/26/2005 1:23:26 PM | P | PART |
|
|
Underground fire supply line flush is satisfactory, pitot reading measured 24 psi. at 4" opening under full flow condition.
|
MIS05-00158
| FIR-Final | 9/26/2005 | 9/26/2005 | 9/26/2005 12:40:39 PM | P | CANC |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Inspection rescheduled for tomorrow 9/27.
|
MIS05-00157
| FIR-Final | 9/26/2005 | 9/26/2005 | 9/26/2005 12:39:28 PM | P | CANC |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Inspection rescheduled for tomorrow 9/27
|
FIR05-00391
| INSP-Final Inspection | 9/23/2005 | 9/26/2005 | 9/26/2005 11:30:58 AM | A | CANC |
|
|
Cancel inspection per Patrick at ###-####, the final location for HVAC diffusers is not complete thus affecting smoke detector location, Patrick to reschedule when ready.
|
FIR05-00429
| INSP-Sprinkler Rough-in/Hydro | 9/23/2005 | 9/26/2005 | 9/26/2005 11:26:25 AM | A | PART |
|
|
Overhead hydrostatic test passed inspection, main tie in is satisfactory, not all drops are cut in at this time.
|
BLD05-02289
| FIRE-Final Inspection | 9/23/2005 | 9/26/2005 | 9/26/2005 10:10:51 AM | A | PASS |
|
|
The provided fire extinguisher was relocated to a normal path of travel while on site, no fire sprinkler or alarm modifications were required, fire life safety passed inspection.
|
BLD04-01413
| FIRE-Final Inspection | 9/26/2005 | 9/26/2005 | 9/26/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled.
|