Inspections for the day of: Wednesday, September 26, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03094 ELE-Aging Inspection9/26/20079/26/200710/2/2007 2:48:21 PM PART
called contr will check staus of job
ELE07-01573 Final9/26/20079/26/20079/27/2007 9:32:02 AMPFAIL
Scheduled by a contractor via Hello! on 9/26/2007 at 9:59:30 AM. Contact: ###-####. corr called 410.8 clearence downstairs bed rm closet fixtures, 110.26(A)&(F)(2) clearence house panel needs 36" 408.4 be specific panel directory house
ELE07-01570 Final9/26/20079/26/20079/27/2007 9:29:53 AMPFAIL
Scheduled by a contractor via Hello! on 9/26/2007 at 9:58:21 AM. Contact: ###-####. corr. called 410.8 clearence downstairs bed rm closet fixtures, 408.4 be specific panel directory house panel
ELE07-01571 Final9/26/20079/26/20079/27/2007 9:28:10 AMPFAIL
Scheduled by a contractor via Hello! on 9/26/2007 at 10:00:25 AM. Contact: ###-####. corr called 210.52(A) needs outlet fixed panel door M bed rm upstairs, to the right, 406.8(C) remove outlet from tub space MB bath, 410.8 clearence downstairs bed rm. closet fixtures, 408.4 panel directory be specific, 100.26(A)&(F)(2) house service shall have required clearence in front of it 36"
ELE06-00711 Electrical Rough-In9/26/20079/26/20079/26/2007 4:34:45 PMPPASS
Scheduled by a contractor via Hello! on 9/26/2007 at 7:03:57 AM. Contact: ###-####. all ceilings 5th floor Gary will fix support for cables
ELE07-03222 Electrical Rough-In9/26/20079/26/20079/26/2007 3:41:16 PMPPASS
steve - homeowner will be there after 2:30 Phone #: ###-#### r/i ok corr. made
ELE07-03337 Temporary Service9/25/20079/26/20079/26/2007 3:14:44 PMPPASS
208###-#### Internet Inspection Request from: Todd Holbrook t/s u/g new ok
ELE07-03349 Rough-In Permanent Service9/26/20079/26/20079/26/2007 2:57:39 PMPFAIL
paul Phone #: ###-#### see added p/s, corr called210.52(B) din rm shall be on SABC note plans state din. rm. not den or office, 334.23 protect all cables within 6ft of attic accesses, outlets left and right of fireplace fam. rm ? is it wall space or are there going to be cabinets plans don't show
ELE07-01939 Final9/25/20079/26/20079/26/2007 1:55:42 PMPNH
The homeowner should be home, if not the garage code is 1211 and the key pad is on the left side of the garage. Thank you and if you have any problems please give me a call at ###-####. Clay Phone #: ###-#### Internet Inspection Request from: Clay Morgan notice posted called owner not home no access
ELE07-03073 Electrical Rough-In9/26/20079/26/20079/26/2007 1:34:10 PMPPASS
phil Phone #: ###-#### r/i ok still needs outlet for counter in kit desk area 2ft 4 ft rule
called contr will install outlet
ELE07-00875 Final9/26/20079/26/20079/26/2007 12:45:13 PMPPASS
All installations are complete for the new sign. please final Phone #: ###-#### Internet Inspection Request from: David Mackey looks ok no access to wiring up high or sign they are lables on signs
ELE07-02064 Conference9/25/20079/26/20079/26/2007 10:59:23 AMADONE
jared Phone #: ok
ELE07-03297 Temporary Service9/25/20079/26/20079/26/2007 10:30:17 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
ELE07-03296 Temporary Service9/25/20079/26/20079/26/2007 10:29:47 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe t/s u/g new ok
ELE07-03221 Electrical Rough-In9/25/20079/26/20079/26/2007 9:56:53 AMAPASS
michael - trench for parking lot lights Phone #: ###-#### ok
ELE07-03221 Final9/26/20079/26/20079/26/2007 9:56:29 AMAPASS
michael - trench for parking lot lights Phone #: ###-#### ok
ELE07-03284 Rough-In Permanent Service9/25/20079/26/20079/26/2007 9:35:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn called survey nail plates and outside boxes not flush r/i ok
p/s u/g new ok
ELE07-03300 Rough-In Permanent Service9/24/20079/26/20079/26/2007 9:03:23 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Rohl corr. called 210.52(C)(1) needs recept left of kit sink, 314.16 box fill, 110.3(A&B) replace broken box pantry, manufactures instructions for mico wave circuit, both high and low voltage wiring nail plates and 11/4" parallel, low voltage 362.30, 362.6 secure ent 3ft of box, use listed fittings,conn at cabinet, do not cover posted
ELE07-03300 Permanent Service9/26/20079/26/20079/26/2007 8:58:57 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dan Rohl p/s u/g new ok