Inspections for the day of: Wednesday, September 26, 2007.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00277 FIR-Aging Inspection9/26/20079/26/200710/3/2007 11:35:47 AM DEFR
FIR07-00538 INSP-Final Inspection9/26/20079/26/20079/27/2007 10:57:27 AMPPART
Some items corrected while on site, noted on plans areas in need of correction including roll up door, adjust cd rating at one device, no access to the womens and mens restroom a/v's, noted construction is still in progress at several areas-need all dust covers removed prior to final acceptance, change descriptor at one duct detector, will verify signals at next inspection.
FIR07-00773 INSP-Final Inspection9/25/20079/26/20079/26/2007 3:21:56 PMPPASS
Fire sprinkler work passed final inspection, contractor to provide QR type heads at the existing riser head box as discussed.
BLD07-00908 FIRE-Final Inspection9/26/20079/26/20079/26/2007 3:19:33 PMPPASS
Items on correction notice verified for compliance, fire life safety inspection passed, contractor to provide "door to remain unlocked while building is occupied" signage at the main entry/exit prior to structural final as discussed, PFE's to be installed at tenant occupancy.
FIR07-00571 INSP-Final Inspection9/26/20079/26/20079/26/2007 3:15:23 PMPPASS
Noted correction items from the previous inspection are completed, permit finaled.
FIR07-00452 INSP-Final Inspection9/25/20079/26/20079/26/2007 3:14:02 PMPPASS
Fire alarm work passed final inspection, permit finaled.
FIR07-00674 INSP-Final Inspection9/20/20079/26/20079/26/2007 3:13:02 PMAPART
Noted three upright heads at mechanical room 000Y which exceed the max. allowable distance below the deck for proper response time- the mech. piping above the heads does not provide adequate heat collection. The remainder of overhead installation is acceptable.