Inspections for the day of: Wednesday, September 26, 2012.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-02542 FIRE-Final Inspection9/26/20129/26/20129/26/2012 3:44:36 PMPFAIL
Provide sticker at the main exit, provide annual inspection for the fire extinguisher, remove the dead bolts, top and bottom, at the main exit, remove the thumbturn deadbolt at the rear exit and provide single action hardware or get plan review approval to cover door since only one exit is required.
BLD12-02310 FIRE-Final Inspection9/26/20129/26/20129/26/2012 3:06:56 PMPPASS
Life safety passed.
FIR12-00477 INSP-Sprinkler Rough-in/Hydro9/26/20129/26/20129/26/2012 2:37:58 PMPPASS
Underground and overhead hydro tests passed.
FIR12-00477 INSP-Supply line flush9/26/20129/26/20129/26/2012 2:36:30 PMPPASS
Underground flush passed.
FIR12-00473 INSP-Final Inspection9/26/20129/26/20129/26/2012 2:01:08 PMPFAIL
All items as far as permit scope of work are completed. The fire alarm panel has existing issues with double addresses and apparently faulty tamper switches. These items need to be corrected/repaired prior to a final sign off on the tenant permit.
BLD12-02488 FIRE-Final Inspection9/25/20129/26/20129/26/2012 12:16:02 PMAFAIL
Provide city approved plans, provide solid pile/racking permit for the product that exceeds 12' in solid pile and the racks that exceed 8' in height, provide single action hardware on the rear exit door, remove the obstructions to the fire extinguishers, verify that the mezzanine storage is shown on the approved plans, remove cardboard at the rear restroom, remove the thumbturn lock at the main exit door and provide sticker as discussed. Keyed hardware is ok at the main exit.
FIR11-00472 FIR-Aging Inspection9/19/20129/26/20129/26/2012 11:54:04 AMAPASS
Permit has beeen finaled
BLD12-02310 FIRE-Supply Line Flush9/26/20129/26/20129/26/2012 11:46:51 AMPCANC
Wrong inspection type
BLD12-01154 FIRE-Final Inspection9/25/20129/26/20129/26/2012 11:25:54 AMAPASS
Life safety passed
FIR12-00511 INSP-Final Inspection9/25/20129/26/20129/26/2012 11:14:10 AMAPASS
Permit finaled
BLD12-01141 FIRE-Final Inspection9/25/20129/26/20129/26/2012 11:13:10 AMAFAIL
Life safety ok to pass when the project related fire alarm and fire sprinkler permits are finaled
FIR12-00362 INSP-Final Inspection9/25/20129/26/20129/26/2012 11:11:46 AMAFAIL
Provide hanger on the armover that exceeds 2'.
BLD12-00149 FIRE-Final Inspection9/25/20129/26/20129/26/2012 9:23:33 AMAPASS
Life safety passed
FIR12-00536 INSP-Final Inspection9/25/20129/26/20129/26/2012 9:22:36 AMAPASS
Permit finaled. Hood suppression system functioned correctly.
BLD12-02291 FIRE-Final Inspection9/25/20129/26/20129/26/2012 8:54:03 AMAFAIL
Remove the thumbturn lock on the main exit (keyed is ok), repair the exit sign at the main exit, provide annual inspection for the fire extinguisher, provide sprinkler protection or remove the ceiling in the new closet, provide single action hardware or remove the door to the new closet, remove the thumbturn lock on the rear exit and provide single action hardware as discussed.
FIR12-00026 FIR-Aging Inspection9/26/20129/26/20129/26/2012 8:09:43 AM NR
Per general contractor the work to fix the sync'ing problem is still being worked on.
FIR12-00109 INSP-Final Inspection9/25/20129/26/20129/26/2012 7:52:06 AMAPASS
Permit finaled