ELE10-01638
| ELE-Aging Inspection | 9/26/2012 | 9/26/2012 | 10/2/2012 7:38:44 AM | | PASS |
|
|
still under construction
|
ELE12-02390
| Electrical Rough-In | 9/26/2012 | 9/26/2012 | 9/26/2012 3:22:45 PM | P | FAIL |
|
|
this is for rough in walls and ceiling Phone #: ###-#### >> Inspection requested via web by Daniel Gamboa Nec 334.30 Shall stable NM cable not more than 4 1/2 ft. from last point of support. All device boxes are required to be made up on rough-in inspection
|
ELE12-02400
| Temporary Service | 9/26/2012 | 9/26/2012 | 9/26/2012 2:21:30 PM | P | PASS |
|
|
Lloyd Phone #: ###-#### t/s u/g n ok
|
ELE12-02401
| Electrical Rough-In | 9/26/2012 | 9/26/2012 | 9/26/2012 2:20:25 PM | P | FAIL |
|
|
access at rear Phone #: ###-#### >> Inspection requested via web by Mark Estep NEC 300.4 Protection against physical damage nail plates NEC 334.30 securing and supporting, stabling
|
GCE12-00103
| GCE-Temporary Service | 9/26/2012 | 9/26/2012 | 9/26/2012 1:24:04 PM | P | NR |
|
|
Temp.pole not on site
|
ELE12-02131
| Final | 9/26/2012 | 9/26/2012 | 9/26/2012 1:05:13 PM | P | PASS |
|
|
Please Provide a final inspection for the Rathbone TI. Contact Cody with any questions. Cody is not on site today, so if you can''t get a hold of him please call Sean ###-####. Thank you and have a great day! Phone #: ###-#### >> Inspection requested via web by Kevin Perez final ok No sign off on site
|
ELE12-02402
| Electrical Rough-In | 9/26/2012 | 9/26/2012 | 9/26/2012 12:32:40 PM | P | PASS |
|
|
We need an under ground inspection on trench from garage to house. Phone #: ###-#### >> Inspection requested via web by Rhonda Yoast rough-in ok cover trench garage to house
|
ELE12-02393
| Electrical Rough-In | 9/26/2012 | 9/26/2012 | 9/26/2012 12:09:01 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by PAT MILLER rough-in ok cover kitchen remodel
|
ELE12-02216
| Electrical Rough-In | 9/25/2012 | 9/26/2012 | 9/26/2012 11:57:49 AM | P | PASS |
|
|
Contact: Paul Perala Phone #: ###-#### >> Inspection requested via web by Deb Gooden rough-in ok cover ceiling grid 3 rooms
|
ELE12-01609
| Final | 9/26/2012 | 9/26/2012 | 9/26/2012 11:35:01 AM | P | NR |
|
|
Please call Adam ###-#### or Drew ###-#### for access. Thank you! Phone #: ###-#### >> Inspection requested via web by Adam Staigle Fourway switching in upstairs hallway and attic fan wiring not completed at this time
|
ELE10-02198
| ELE-Aging Inspection | 9/26/2012 | 9/26/2012 | 9/26/2012 11:23:34 AM | | DONE |
|
|
contractor will contact homeowner for access
|
ELE12-02148
| Electrical Rough-In | 9/25/2012 | 9/26/2012 | 9/26/2012 11:06:25 AM | A | PASS |
|
|
dirt work Phone #: ###-#### >> Inspection requested via web by Erick Baker rough-in ok cover underground, conduits under slab
|
ELE12-02121
| Final | 9/25/2012 | 9/26/2012 | 9/26/2012 10:47:43 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by John VanZandt Quad receptacle in bedroom has no equipment grounding conductor or GFCI protection
|
ELE12-02398
| Electrical Rough-In | 9/25/2012 | 9/26/2012 | 9/26/2012 10:30:46 AM | A | PASS |
|
|
For access please call Matt 1/2 hr prior to inspection. ###-#### Phone #: ###-#### >> Inspection requested via web by Terry Scott rough-in ok cover bedroom only, laundry room not ready at this time
|
ELE12-02396
| Temporary Service | 9/26/2012 | 9/26/2012 | 9/26/2012 9:59:55 AM | A | PASS |
|
|
Call Dene with any questions Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser t/s u/g n ok
|
ELE12-01760
| Final | 9/25/2012 | 9/26/2012 | 9/26/2012 9:41:21 AM | A | PASS |
|
|
cell ###-#### Phone #: ###-#### >> Inspection requested via web by Mark M final ok
|
ELE12-02399
| Final | 9/26/2012 | 9/26/2012 | 9/26/2012 9:26:56 AM | A | PASS |
|
|
for fees due final ok
|
ELE12-02399
| Rough-In Permanent Service | 9/25/2012 | 9/26/2012 | 9/26/2012 9:26:16 AM | A | PASS |
|
|
THIS IS THE FEE DUE PART SO SHOUNDNT THIS ONE BE TAKEN AS A FINAL???? PLEAE CANGE IT ON YOU COMOUTER SO I DONT SEE IT ANY MORE, THANKS BOB rough-in ok thank you, and I will final this permit
YOUR THE MAN Phone #: ###-#### >> Inspection requested via web by Bob Glenn
|
ELE12-02318
| Rough-In Permanent Service | 9/25/2012 | 9/26/2012 | 9/26/2012 9:23:12 AM | A | PASS |
|
|
TANKS, BILL Phone #: ###-#### >> Inspection requested via web by Bob Glenn rough-in p/s u/g n ok
|
ELE12-02200
| Permanent Service | 9/25/2012 | 9/26/2012 | 9/26/2012 9:08:12 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Patrick Paz p/s o/h rec ok
|
ELE12-02257
| Permanent Service | 9/25/2012 | 9/26/2012 | 9/25/2012 2:39:51 PM | A | PASS |
|
|
Mike Phone #: ###-#### p/s u/g n meter pac ok
|
ELE12-01920
| Final | 9/25/2012 | 9/26/2012 | 9/25/2012 1:58:28 PM | A | PASS |
|
|
Hello, please provide a final inspection for the Planet Fitness project. Contact Ron ###-####. Have a great day! Phone #: ###-#### >> Inspection requested via web by Kevin Perez final ok
|