FIR06-00062
| FIR-Aging Inspection | 9/26/2014 | 9/26/2014 | 10/2/2014 7:48:13 AM | | NR |
|
|
Contractor is out of business and sold accounts to Taylor Brothers.
|
BLD13-03253
| FIRE-Final Inspection | 9/26/2014 | 9/26/2014 | 9/26/2014 3:47:49 PM | P | FAIL |
|
|
Provide single action hardware for the interior doors, provide one hour rated fire riser room, provide knox box and placement by the boise city fire dept., provide final inspections for the project related fire sprinkler and fire alarm permits.
|
FIR13-00697
| INSP-Sprinkler Rough-in/Hydro | 9/26/2014 | 9/26/2014 | 9/26/2014 3:06:14 PM | P | PASS |
|
|
See the city approved plans for new area where piping can be covered.
|
FIR14-00300
| INSP-Final Inspection | 9/25/2014 | 9/26/2014 | 9/26/2014 3:05:06 PM | P | FAIL |
|
|
Provide certification of backflow, provide forward flush test, replace painted heads. 24 hour air test has not been performed. Air test started with pressure marked on the guage.
|
FIR14-00177
| INSP-Final Inspection | 9/25/2014 | 9/26/2014 | 9/26/2014 3:03:40 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00364
| INSP-Final Inspection | 9/25/2014 | 9/26/2014 | 9/26/2014 3:03:14 PM | P | FAIL |
|
|
Provide map and document box.
|
BLD13-02490
| FIRE-Final Inspection | 9/26/2014 | 9/26/2014 | 9/26/2014 1:36:44 PM | P | PASS |
|
|
life safety passed
|
FIR14-00609
| INSP-Sprinkler Rough-in | 9/25/2014 | 9/26/2014 | 9/26/2014 10:45:42 AM | A | PASS |
|
|
Rough-in passed. Piping can be finaled
|
FIR14-00585
| INSP-Final Inspection | 9/26/2014 | 9/26/2014 | 9/26/2014 10:45:02 AM | P | PASS |
|
|
Permit finaled
|
BLD13-00906
| FIRE-Final Inspection | 9/26/2014 | 9/26/2014 | 9/26/2014 9:56:06 AM | P | FAIL |
|
|
To complete the life safety in the new office area only I need the fire alarm system corrections completed and all of the emergency lights and exit signs installed and functional.
|
FIR14-00095
| INSP-Final Inspection | 9/26/2014 | 9/26/2014 | 9/26/2014 9:54:56 AM | P | FAIL |
|
|
To complete the fire alarm in the new area I need the 110 power of the elevator monitored and the door mags to release upon general alarm.
|
BLD14-00461
| FIRE-Final Inspection | 9/25/2014 | 9/26/2014 | 9/26/2014 9:41:24 AM | A | PASS |
|
|
Life safety passed.
|