Inspections for the day of: Friday, September 26, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00062 FIR-Aging Inspection9/26/20149/26/201410/2/2014 7:48:13 AM NR
Contractor is out of business and sold accounts to Taylor Brothers.
BLD13-03253 FIRE-Final Inspection9/26/20149/26/20149/26/2014 3:47:49 PMPFAIL
Provide single action hardware for the interior doors, provide one hour rated fire riser room, provide knox box and placement by the boise city fire dept., provide final inspections for the project related fire sprinkler and fire alarm permits.
FIR13-00697 INSP-Sprinkler Rough-in/Hydro9/26/20149/26/20149/26/2014 3:06:14 PMPPASS
See the city approved plans for new area where piping can be covered.
FIR14-00300 INSP-Final Inspection9/25/20149/26/20149/26/2014 3:05:06 PMPFAIL
Provide certification of backflow, provide forward flush test, replace painted heads. 24 hour air test has not been performed. Air test started with pressure marked on the guage.
FIR14-00177 INSP-Final Inspection9/25/20149/26/20149/26/2014 3:03:40 PMPPASS
Permit finaled
FIR14-00364 INSP-Final Inspection9/25/20149/26/20149/26/2014 3:03:14 PMPFAIL
Provide map and document box.
BLD13-02490 FIRE-Final Inspection9/26/20149/26/20149/26/2014 1:36:44 PMPPASS
life safety passed
FIR14-00609 INSP-Sprinkler Rough-in9/25/20149/26/20149/26/2014 10:45:42 AMAPASS
Rough-in passed. Piping can be finaled
FIR14-00585 INSP-Final Inspection9/26/20149/26/20149/26/2014 10:45:02 AMPPASS
Permit finaled
BLD13-00906 FIRE-Final Inspection9/26/20149/26/20149/26/2014 9:56:06 AMPFAIL
To complete the life safety in the new office area only I need the fire alarm system corrections completed and all of the emergency lights and exit signs installed and functional.
FIR14-00095 INSP-Final Inspection9/26/20149/26/20149/26/2014 9:54:56 AMPFAIL
To complete the fire alarm in the new area I need the 110 power of the elevator monitored and the door mags to release upon general alarm.
BLD14-00461 FIRE-Final Inspection9/25/20149/26/20149/26/2014 9:41:24 AMAPASS
Life safety passed.