ELE16-02373
| Final | 9/22/2016 | 9/26/2016 | 9/26/2016 2:18:57 PM | P | PASS |
|
|
Justin-Please call 30 minutes prior Phone #: ###-#### Final for re-switch and plug 8 plex ok
|
ELE16-03105
| Final | 9/23/2016 | 9/26/2016 | 9/26/2016 2:02:02 PM | P | PASS |
|
|
Both 22 and 23 our on the same pole. any questions please call david. Phone #: ###-#### Inspection requested via web by Charmel Kubik Idaho power had already energized service Final ok
|
ELE16-03104
| Final | 9/23/2016 | 9/26/2016 | 9/26/2016 2:01:20 PM | P | PASS |
|
|
Any questions please call david Phone #: ###-#### Inspection requested via web by Charmel Kubik idaho power already energized prior to inspection final ok
|
ELE16-03123
| Electrical Rough-In | 9/26/2016 | 9/26/2016 | 9/26/2016 1:54:38 PM | P | PASS |
|
|
Upher ground inspection Phone #: ###-#### Inspection requested via web by Ben Archibald concrete encased electrode ok pour
|
ELE16-02770
| Final | 9/26/2016 | 9/26/2016 | 9/26/2016 1:15:51 PM | P | CANC |
|
|
Call Barry if you have any questions. Phone #: ###-#### Inspection requested via web by Thaniel Bishop no access/nobody home
|
ELE16-02186
| Final | 9/26/2016 | 9/26/2016 | 9/26/2016 12:34:28 PM | P | CANC |
|
|
Final for kitchen remodel, laundry/powder bath remodel, master bed and bath remodel Phone #: ###-#### Inspection requested via web by Jarod Murray nobody home
|
ELE16-03077
| Final | 9/26/2016 | 9/26/2016 | 9/26/2016 12:27:18 PM | P | PASS |
|
|
jr Phone #: ###-#### final for service change and exterior receptacles ok
|
ELE16-02774
| Final | 9/24/2016 | 9/26/2016 | 9/26/2016 9:27:17 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by George Pascua 406.4 all 120v receptacles shall be tamper resistant (kitchen plug mold) 110.7 & 410.10 tub cans not installed and shall be enclosed
|
ELE16-02161
| Final | 9/23/2016 | 9/26/2016 | 9/26/2016 8:58:14 AM | A | PASS |
|
|
lock box code is 4750. Call Jared with any questions ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan Corrections fixed final ok
|
ELE16-02160
| Final | 9/23/2016 | 9/26/2016 | 9/26/2016 8:57:50 AM | A | PASS |
|
|
Lock box code is 4750. Call Jared with any questions ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan Corrections fixed final ok
|
ELE16-01823
| Final | 9/23/2016 | 9/26/2016 | 9/26/2016 8:57:25 AM | A | PASS |
|
|
Lock box code is 4750. Call Jared with any questions ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan Corrections fixed final ok
|