Inspections for the day of: Tuesday, September 26, 2017.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-04319 Final9/25/20179/26/20179/26/2017 4:02:38 PMPPASS
please call our lead installer Dakoda when 30 mins in route Phone #: ###-#### Inspection requested via web by Rick Montgomery
MEC17-03090 Final9/21/20179/26/20179/26/2017 3:28:44 PMPPASS
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 3 :00 PM . Contact for Right Now is Mary ###-####

Phone #: ###-#### Inspection requested via web by Mary LaFayette- 5lb flue pass
MEC17-04317 Final9/26/20179/26/20179/26/2017 2:53:29 PMPNR
Aleks ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- venting not complete, flue missing
MEC17-04317 Pressure Test9/26/20179/26/20179/26/2017 2:52:52 PMPPASS
Aleks ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- 20lb gas pass- not tied into meter- underground to shop ok- ok to back fill
MEC17-02395 Final9/20/20179/26/20179/26/2017 2:19:48 PMPPASS
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 1:30 . Contact for Right Now is Mary ###-####
Phone #: ###-#### Inspection requested via web by Mary LaFayette- 5lb flue pass
MEC17-04310 Final9/26/20179/26/20179/26/2017 1:53:13 PMPCANC
Please contact homeowner with an estimated time, she has to take time off to meet you Phone #: ###-#### Inspection requested via web by Dianne Maxwell - per phone call with homeowner we reschedule this for thursday afternnon
MEC17-03704 Final9/26/20179/26/20179/26/2017 12:52:07 PMPPASS
MEC17-04282 Final9/26/20179/26/20179/26/2017 12:51:48 PMPPASS
MEC17-04189 Rough-in9/25/20179/26/20179/26/2017 11:33:04 AMAPASS
James Phone #: ###-####
MEC17-04189 Pressure Test9/26/20179/26/20179/26/2017 11:32:39 AMAPASS
James Phone #: ###-####- 20lb gas pass
MEC17-03281 Final9/21/20179/26/20179/26/2017 11:16:32 AMAPASS
please call homeowner David when 30 mins in route for AM request- Thank you Phone #: ###-#### Inspection requested via web by Rick Montgomery- correction made
MEC16-05276 Mec-Aging Inspection9/26/20179/26/20179/26/2017 10:26:40 AM PART
need dante valve installed on other mec permit before this permit can be final out
MEC17-04211 Final9/25/20179/26/20179/26/2017 10:05:29 AMAFAIL
Hello! This came back as NR last Friday. The client requests a timeframe of about 10:00am. I told him I could not guarantee, but that I would ask. His # to call ###-####. His name is John McMahon.

Thank you! Phone #: ###-#### Inspection requested via web by Rick Borg- R/A plenum in garage needs insulated with R6 insulation unconditioned space
MEC17-03581 Final9/25/20179/26/20179/26/2017 9:50:25 AMAPART
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- gas line on roof needs supported to roof stands- need to look at R/A in northwest office prints show in room installed in hallway- temp occupancy ok no card onsite to sign
MEC17-04094 Rough-in9/25/20179/26/20179/26/2017 9:13:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Joseph Profitt- intake for water heater will be ran on final after water heater is set- need make up air grill for dryer in closet or vent from outside
MEC17-04094 Pressure Test9/25/20179/26/20179/26/2017 9:11:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Joseph Profitt- 20lb gas pass- 5lb flue x 2 pass-
MEC17-04310 Final9/25/20179/26/20179/25/2017 3:57:00 PMPPASS
Please contact homeowner with an estimated time, she has to take time off to meet you Phone #: ###-#### Inspection requested via web by Dianne Maxwell