Inspections for the day of: Tuesday, September 26, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03217 Permanent Service9/26/20179/26/20179/26/2017 1:43:15 PMPCANC
Phone #: ###-#### Inspection requested via web by Alan Lusk
ELE17-03002 Final9/26/20179/26/20179/26/2017 1:27:23 PMPPASS
Final on solar array Phone #: ###-#### Inspection requested via web by Paula Gietzen Ok final.
ELE17-02288 Final9/26/20179/26/20179/26/2017 1:27:22 PMPFAIL
Phone #: ###-#### Inspection requested via web by Bob Glenn
1. Up beds E side not ARC fault protected.
2. 2 gang blank needed in garage for 10/3.
3 Toggle switch needed for up furnace. 422.35
ELE17-03209 Final9/25/20179/26/20179/26/2017 12:09:11 PMPPASS
Please final Phone #: ###-#### Inspection requested via web by David Mackey Ok final. Talked to contractor. Existing lighting switch was used to power an in-line exhaust fan, and 1 recept was added on W wall.
ELE17-03161 Final9/26/20179/26/20179/26/2017 12:07:33 PMAPASS
Thank you ; have a lovely day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Ok final. Breakered at 60a with #6
ELE17-03042 Electrical Rough-In9/26/20179/26/20179/26/2017 12:06:16 PMPPASS
I will meet you on site with a Panel and optimizer to show UL Listings of all equipment. Please Call or Text me when you are about to head to the job so I have time to meet you there. Thanks,
###-#### Phone #: ###-#### Inspection requested via web by Jesse Simpson All components UL listed.
ELE17-02957 Conference9/25/20179/26/20179/26/2017 11:22:46 AMADONE
Discuss service disconnect options and grounding. Phone #: ###-#### Inspection requested via web by Chase Sessions Discussed the need for seperate equipt grounds in each raceway 250.122 (F)(1)(B). Spliced conductors 230.46., and the need for a 3rd disconnect for panel 310.10(H). Someone had cut all conductors off to a non-working length. Gutters are needed to extend to working length.
ELE17-01479 Final9/25/20179/26/20179/26/2017 9:40:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Tracy Robertson Ok final.
ELE17-03158 Rough-In Permanent Service9/25/20179/26/20179/26/2017 9:20:55 AMAPASS
Any questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren p/s u/g n ok. Talked to contractor about expanding the expansion coupling and adding mud ring downstairs NE bed N wall for ufer.
ELE17-03211 Temporary Service9/25/20179/26/20179/26/2017 8:47:13 AMAPASS
Phone #: ###-#### Inspection requested via web by Rhonda Yoast t/s o/h n ok