FIR06-00346
| INSP-Final Inspection | 9/22/2006 | 9/27/2006 | 9/28/2006 7:59:59 AM | P | PASS |
|
|
Fire sprinkler final inspection passed, permit finaled.
|
FIR06-00679
| INSP-Sprinkler Rough-in | 9/27/2006 | 9/27/2006 | 9/28/2006 7:58:31 AM | P | PART |
|
|
OH fire sprinkler rough-in is good for cover at the drop ceiling areas.
|
BLD06-00377
| FIRE-Final Inspection | 9/26/2006 | 9/27/2006 | 9/27/2006 2:43:33 PM | P | FAIL |
|
|
Need address numbers facing Gowen road, exit signs do not illuminate on battery backup, provide visual indicator at the main entry/exit door, one emergency light does not function, need to provide means to test the two duct smoke detectors, the shell permit must be finaled prior to TI final.
|
BLD06-02318
| FIRE-Final Inspection | 9/25/2006 | 9/27/2006 | 9/27/2006 2:40:07 PM | P | PASS |
|
|
Life safety passed inspection, one fire extinguisher relocated as discussed.
|
FIR06-00376
| INSP-Alarm Testing | 9/26/2006 | 9/27/2006 | 9/27/2006 2:38:22 PM | A | PART |
|
|
Remainder of fire alarm work passed inspection except one pair doors on the main level which failed to properly close upon activation of the adjacent smoke detector.
|
FIR06-00579
| INSP-Alarm Testing | 9/22/2006 | 9/27/2006 | 9/27/2006 2:35:56 PM | A | PASS |
|
|
Fire alarm passed field testing, need to provide record of completion for signature to final permit.
|
FIR06-00251
| INSP-Final Inspection | 9/25/2006 | 9/27/2006 | 9/27/2006 10:24:26 AM | A | PASS |
|
|
Fire sprinkler passed final inspection, permit finaled.
|
FIR06-00434
| INSP-Sprinkler Rough-in | 9/26/2006 | 9/27/2006 | 9/27/2006 10:13:31 AM | A | PART |
|
|
OH rough-in is acceptable pending spacing at NE and SE overbuilds and revision of the ball drip location on the FDC for proper functionality.
|
FIR05-00425
| INSP-Sprinkler Rough-in | 9/26/2006 | 9/27/2006 | 9/27/2006 10:09:58 AM | A | PART |
|
|
OH rough-in at the drop ceiling areas for the 5th floor corridors and pool room are good for cover, 11th floor corridor drop ceiling is also acceptable for cover.
|
FIR06-00665
| INSP-Final Inspection | 9/26/2006 | 9/27/2006 | 9/27/2006 10:05:24 AM | A | FAIL |
|
|
Need to provide updated map at the panel for added in-duct detector locations, the beam pocket above the new NAC panel will require a smoke detector. Notification devices and in-duct detectors tested okay.
|