Inspections for the day of: Wednesday, September 27, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00346 INSP-Final Inspection9/22/20069/27/20069/28/2006 7:59:59 AMPPASS
Fire sprinkler final inspection passed, permit finaled.
FIR06-00679 INSP-Sprinkler Rough-in9/27/20069/27/20069/28/2006 7:58:31 AMPPART
OH fire sprinkler rough-in is good for cover at the drop ceiling areas.
BLD06-00377 FIRE-Final Inspection9/26/20069/27/20069/27/2006 2:43:33 PMPFAIL
Need address numbers facing Gowen road, exit signs do not illuminate on battery backup, provide visual indicator at the main entry/exit door, one emergency light does not function, need to provide means to test the two duct smoke detectors, the shell permit must be finaled prior to TI final.
BLD06-02318 FIRE-Final Inspection9/25/20069/27/20069/27/2006 2:40:07 PMPPASS
Life safety passed inspection, one fire extinguisher relocated as discussed.
FIR06-00376 INSP-Alarm Testing9/26/20069/27/20069/27/2006 2:38:22 PMAPART
Remainder of fire alarm work passed inspection except one pair doors on the main level which failed to properly close upon activation of the adjacent smoke detector.
FIR06-00579 INSP-Alarm Testing9/22/20069/27/20069/27/2006 2:35:56 PMAPASS
Fire alarm passed field testing, need to provide record of completion for signature to final permit.
FIR06-00251 INSP-Final Inspection9/25/20069/27/20069/27/2006 10:24:26 AMAPASS
Fire sprinkler passed final inspection, permit finaled.
FIR06-00434 INSP-Sprinkler Rough-in9/26/20069/27/20069/27/2006 10:13:31 AMAPART
OH rough-in is acceptable pending spacing at NE and SE overbuilds and revision of the ball drip location on the FDC for proper functionality.
FIR05-00425 INSP-Sprinkler Rough-in9/26/20069/27/20069/27/2006 10:09:58 AMAPART
OH rough-in at the drop ceiling areas for the 5th floor corridors and pool room are good for cover, 11th floor corridor drop ceiling is also acceptable for cover.
FIR06-00665 INSP-Final Inspection9/26/20069/27/20069/27/2006 10:05:24 AMAFAIL
Need to provide updated map at the panel for added in-duct detector locations, the beam pocket above the new NAC panel will require a smoke detector. Notification devices and in-duct detectors tested okay.