BLD06-00007
| FIRE-Final Inspection | 9/27/2006 | 9/27/2006 | 9/28/2006 10:57:34 AM | P | CANC |
|
|
Duplicate inspection
|
FIR06-00388
| INSP-Final Inspection | 9/26/2006 | 9/27/2006 | 9/28/2006 10:15:20 AM | A | PASS |
|
|
permit finaled
|
FIR06-00137
| INSP-Supply line flush | 9/27/2006 | 9/27/2006 | 9/27/2006 5:49:58 PM | P | PASS |
|
|
Underground flush passed.
|
MIS06-00226
| FIR-Final | 9/27/2006 | 9/27/2006 | 9/27/2006 3:33:37 PM | P | FAIL |
|
|
Remove the keyed deadbolt and round knob on the rear exit door. Lever hardware or crashbar is ok.
|
BLD06-01567
| FIRE-Final Inspection | 9/26/2006 | 9/27/2006 | 9/27/2006 3:31:56 PM | A | NR |
|
|
Life safety not ready. Sprinkler piping is ok to cover.
|
BLD06-01568
| FIRE-Final Inspection | 9/26/2006 | 9/27/2006 | 9/27/2006 3:31:41 PM | A | NR |
|
|
Life safety not ready. Sprinkler piping is ok to cover.
|
BLD06-01569
| FIRE-Final Inspection | 9/26/2006 | 9/27/2006 | 9/27/2006 3:31:23 PM | A | NR |
|
|
Life safety not ready. Sprinkler piping is ok to cover.
|
BLD06-01827
| FIRE-Conference | 9/26/2006 | 9/27/2006 | 9/27/2006 3:29:13 PM | A | DONE |
|
|
I went over egress lighting and exit sign locations with the contractor.
|
FIR06-00578
| INSP-Sprinkler Rough-in/Hydro | 9/26/2006 | 9/27/2006 | 9/27/2006 10:47:32 AM | A | PASS |
|
|
Sprinkler piping above the ceilings is ok to cover.
|
FIR06-00094
| INSP-Final Inspection | 9/26/2006 | 9/27/2006 | 9/26/2006 4:44:13 PM | A | CANC |
|
|
Troy, We like to schedule for a early AM test. Please call us. Thank You; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|