Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00633 FIRE-Final Inspection9/26/20079/27/200710/1/2007 1:35:01 PMACANC
Tom; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
BLD07-01201 FIRE-Final Inspection9/27/20079/27/20079/28/2007 3:23:44 PMPPASS
The insulation backing in tenant space 10390 has been completed
BLD07-01468 FIRE-Final Inspection9/27/20079/27/20079/28/2007 8:04:10 AMPFAIL
Mount the fire extinguishers and provide exit discharge ligting at all of the exit doors.
FIR07-00797 INSP-Final Inspection9/27/20079/27/20079/28/2007 7:55:35 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Wayne Berry
FIR07-00685 INSP-Final Inspection9/27/20079/27/20079/27/2007 2:32:40 PMPPASS
permit finaled
FIR07-00659 INSP-Final Inspection9/25/20079/27/20079/27/2007 2:31:36 PMPPASS
Permit finaled
BLD06-03212 FIRE-Final Inspection9/27/20079/27/20079/27/2007 2:10:34 PM CANC
Life safety passed
FIR07-00237 INSP-Final Inspection9/27/20079/27/20079/27/2007 2:08:25 PM PASS
Permit finaled
FIR07-00735 INSP-Sprinkler Rough-in9/26/20079/27/20079/27/2007 1:58:03 PMPPART
The 24 hour air test for the Garden Center was started at 11:00 with 55 psi on the guage.
BLD06-01572 FIRE-Final Inspection9/27/20079/27/20079/27/2007 1:56:53 PMPPASS
Life safety passed.
BLD07-01849 FIRE-Final Inspection9/26/20079/27/20079/27/2007 1:53:16 PMAFAIL
Install the ceiling tile
BLD07-02102 FIRE-Final Inspection9/26/20079/27/20079/27/2007 12:48:25 PMAPASS
life safety passed.
BLD07-01718 FIRE-Final Inspection9/26/20079/27/20079/27/2007 12:45:29 PMAFAIL
No access into the space and ceiling tile is not installed.
FIR07-00746 INSP-Final Inspection9/26/20079/27/20079/27/2007 11:53:10 AMAPASS
permit finaled
FIR07-00602 INSP-Final Inspection9/26/20079/27/20079/27/2007 11:49:26 AMACANC
Canceled per mike Phone #: ###-####
FIR07-00582 INSP-Sprinkler Rough-in9/26/20079/27/20079/27/2007 10:43:16 AMAPASS
The spirnkler piping is ok to cover.
FIR07-00585 INSP-Sprinkler Rough-in9/26/20079/27/20079/27/2007 10:42:18 AMAPASS
The spirnkler piping is ok to cover.