Inspections for the day of: Tuesday, September 27, 2011.
Number of inspections: 13
Percentage of inspections complete: 85 %
Percentage of inspections not complete: 15 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00346 INSP-Final Inspection9/20/20119/21/2011 P 
Please cantact Jeremy at ###-####. This inspection is for a school and will need to be scheduled for 3pm or later so classes will not be disrupted. Thank you. Phone #: ###-#### >> Inspection requested via web by David Dilley
FIR08-00239 INSP-Sprinkler Rough-in9/22/20119/22/2011 P 
lonnie Phone #: ###-####
FIR11-00447 INSP-Final Inspection9/21/20119/27/20119/30/2011 12:26:57 PMPNR
Field inspection passed pending repair of visual and audible indicators at the panel for alarm and trouble conditions.
FIR11-00257 INSP-Sprinkler Rough-in/Hydro9/23/20119/27/20119/28/2011 4:39:04 PMPPART
Partial for hydrostatic testing of two branchlines prior to system tie-in.
FIR11-00456 INSP-Sprinkler Rough-in/Hydro9/23/20119/27/20119/28/2011 4:35:36 PMPNR
Plans are not consistent with the field installation.
BLD11-01627 FIRE-Final Inspection9/22/20119/27/20119/28/2011 4:28:16 PMPFAIL
Correction items include; install approved hardware at both restroom doors, provide current certification tags on the PFE's at the east building, project related fire alarm permit final pending. Remainder of inspection items passed.
FIR11-00486 INSP-Final Inspection9/27/20119/27/20119/27/2011 2:12:12 PMPPASS
Fire sprinkler permit finaled.
FIR11-00251 INSP-Final Inspection9/22/20119/27/20119/27/2011 1:11:55 PMAPASS
Inspection passed. Fire alarm permit finaled.
FIR11-00273 INSP-Final Inspection9/22/20119/27/20119/27/2011 1:10:49 PMAPART
Functional testing passed, however the FACP on site is not a 5808 as indicated in the permit documents. A plan modification will be necessary prior to permit final.
FIR11-00291 INSP-Final Inspection9/22/20119/27/20119/27/2011 12:17:04 PMAPASS
Functional testing passed. Scope of work completed, permit finaled.
FIR11-00487 INSP-Sprinkler Rough-in9/26/20119/27/20119/27/2011 11:48:55 AMAPART
Fire sprinkler system modifications per the scope of work are approved for cover.
FIR11-00518 INSP-Sprinkler Rough-in9/26/20119/27/20119/27/2011 11:41:50 AMAPART
Overhead fire sprinkler work okayed for cover at the grid ceilings within the remodel area.
FIR11-00250 INSP-Final Inspection9/22/20119/27/20119/27/2011 11:06:34 AMACANC
Tim Christopherson Phone #: ###-#### >> Inspection requested via web by Diane Turner Inspection cancelled from web by: Diane Turner