FIR10-00346
| INSP-Final Inspection | 9/20/2011 | 9/21/2011 | | P | |
|
|
Please cantact Jeremy at ###-####. This inspection is for a school and will need to be scheduled for 3pm or later so classes will not be disrupted. Thank you. Phone #: ###-#### >> Inspection requested via web by David Dilley
|
FIR08-00239
| INSP-Sprinkler Rough-in | 9/22/2011 | 9/22/2011 | | P | |
|
|
lonnie Phone #: ###-####
|
FIR11-00447
| INSP-Final Inspection | 9/21/2011 | 9/27/2011 | 9/30/2011 12:26:57 PM | P | NR |
|
|
Field inspection passed pending repair of visual and audible indicators at the panel for alarm and trouble conditions.
|
FIR11-00257
| INSP-Sprinkler Rough-in/Hydro | 9/23/2011 | 9/27/2011 | 9/28/2011 4:39:04 PM | P | PART |
|
|
Partial for hydrostatic testing of two branchlines prior to system tie-in.
|
FIR11-00456
| INSP-Sprinkler Rough-in/Hydro | 9/23/2011 | 9/27/2011 | 9/28/2011 4:35:36 PM | P | NR |
|
|
Plans are not consistent with the field installation.
|
BLD11-01627
| FIRE-Final Inspection | 9/22/2011 | 9/27/2011 | 9/28/2011 4:28:16 PM | P | FAIL |
|
|
Correction items include; install approved hardware at both restroom doors, provide current certification tags on the PFE's at the east building, project related fire alarm permit final pending. Remainder of inspection items passed.
|
FIR11-00486
| INSP-Final Inspection | 9/27/2011 | 9/27/2011 | 9/27/2011 2:12:12 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR11-00251
| INSP-Final Inspection | 9/22/2011 | 9/27/2011 | 9/27/2011 1:11:55 PM | A | PASS |
|
|
Inspection passed. Fire alarm permit finaled.
|
FIR11-00273
| INSP-Final Inspection | 9/22/2011 | 9/27/2011 | 9/27/2011 1:10:49 PM | A | PART |
|
|
Functional testing passed, however the FACP on site is not a 5808 as indicated in the permit documents. A plan modification will be necessary prior to permit final.
|
FIR11-00291
| INSP-Final Inspection | 9/22/2011 | 9/27/2011 | 9/27/2011 12:17:04 PM | A | PASS |
|
|
Functional testing passed. Scope of work completed, permit finaled.
|
FIR11-00487
| INSP-Sprinkler Rough-in | 9/26/2011 | 9/27/2011 | 9/27/2011 11:48:55 AM | A | PART |
|
|
Fire sprinkler system modifications per the scope of work are approved for cover.
|
FIR11-00518
| INSP-Sprinkler Rough-in | 9/26/2011 | 9/27/2011 | 9/27/2011 11:41:50 AM | A | PART |
|
|
Overhead fire sprinkler work okayed for cover at the grid ceilings within the remodel area.
|
FIR11-00250
| INSP-Final Inspection | 9/22/2011 | 9/27/2011 | 9/27/2011 11:06:34 AM | A | CANC |
|
|
Tim Christopherson Phone #: ###-#### >> Inspection requested via web by Diane Turner Inspection cancelled from web by: Diane Turner
|