Inspections for the day of: Tuesday, September 27, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00483 INSP-Sprinkler Rough-in9/27/20119/27/20119/28/2011 7:19:10 AMPPASS
Underground cover inspection passed. Piping can be covered.
BLD11-02263 FIRE-Final Inspection9/27/20119/27/20119/27/2011 2:56:21 PMPFAIL
See the city approved plans for a list of corrections. They include a separate permit for sprinkler modifications, annual inspection tag for the fire extinguisher, providing address and removing the thumbturn lock on the exit door.
FIR11-00464 INSP-Sprinkler Rough-in/Hydro9/26/20119/27/20119/27/2011 2:29:33 PMAPASS
The underground hydro test passed.
FIR11-00498 INSP-Final Inspection9/26/20119/27/20119/27/2011 2:28:48 PMAFAIL
Everything functioned except the lights under the hood did not shut off when the system activated.
BLD10-02666 FIRE-Conference9/26/20119/27/20119/27/2011 12:08:14 PMADONE
I discussed the installation of insulation in the combustible concealed spaces with the insulation contractor.
FIR11-00332 INSP-Sprinkler Rough-in9/26/20119/27/20119/27/2011 12:07:12 PMAPASS
Overhead rough-in passed. One pendant needs to be relocated in the corridor. Also the bathroom plan shows a door separating the shower from the remaining restroom. If this separation is not installed the combined space will exceed 50 sq. ft and will require sprinkler protection.
FIR11-00490 INSP-Sprinkler Rough-in9/26/20119/27/20119/27/2011 12:03:29 PMAPASS
Sprinkler piping is ok to cover.
BLD09-00832 FIRE-Final Inspection9/23/20119/27/20119/27/2011 12:00:00 AMACANC
Jesse Phone #: ###-####