Inspections for the day of: Thursday, September 27, 2012.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00612 FIRE-Final Inspection9/25/20129/27/20129/27/2012 3:51:24 PMPPASS
Life safety passed
FIR12-00490 INSP-Sprinkler Rough-in9/26/20129/27/20129/27/2012 3:40:49 PMPPASS
Underground supply line is ok to cover. I noted that two additional (four total) 45 degree fittings have been installed and will need to be included in the hydraulic calculations for the overhead sprinkler system.
FIR12-00174 INSP-Sprinkler Rough-in9/27/20129/27/20129/27/2012 2:39:19 PMPPART
Sprinkler rough-in is passed but the sprinkler heads in the corridor as shown on the plans are to be large orfice but as installed are not. I spoke to Jim and he is going to address this issue with Tim Frost.
FIR12-00288 INSP-Sprinkler Rough-in9/25/20129/27/20129/27/2012 2:26:52 PMAPART
Sprinkler piping above lay-in ceiling tle can be covered. Issues that need addressed prior to a final sign off are missing upright head at one location, overspaced upright heads at another location, standard responce (existing) pendants installed in rooms where per the plans the heads are to be changed to quick responce, standard and quick responce heads mixed in the same compartment and areas with no sprinkler protection due to soffits. Ceiling plans does not match either due to ceilings installed where none were shown and soffits/low ceilings that have either been deleted or relocated. Contact plan review for guidance on resubmittals/as-builts.
FIR12-00469 INSP-Final Inspection9/27/20129/27/20129/27/2012 2:13:27 PMPPASS
Permit finaled
FIR12-00459 INSP-Final Inspection9/27/20129/27/20129/27/2012 2:12:15 PMPFAIL
All ceiling tile and sprinkler canopies have not been installed yet
FIR11-00435 INSP-Final Inspection9/26/20129/27/20129/27/2012 9:37:45 AMACANC
I spoke to Brian Giacomino about the plans needing to be resubmitted due to device change out and new NAC panel installation.
FIR12-00174 FIR-Aging Inspection9/27/20129/27/20129/27/2012 9:02:44 AM PASS
Rough-in inspection scheduled
BLD12-01141 FIRE-Final Inspection9/27/20129/27/20129/27/2012 8:27:52 AMPPART
Life safety passed. Exit signs being used are "nuclear" type. They have no obvious expiration date but do have the UL stamp.
Waiting for Phase 2 per Troy Cobbley
FIR12-00473 INSP-Final Inspection9/26/20129/27/20129/27/2012 8:26:43 AMAPASS
Permit finaled. Trouble conditions on the fire alarm panel have been cleared.
FIR12-00362 INSP-Final Inspection9/26/20129/27/20129/27/2012 8:26:06 AMAPART
Permit finaled. Hanger has been added. Waiting for Phase 2 per Troy Cobbley
FIR12-00133 INSP-Final Inspection9/27/20129/27/20129/27/2012 8:24:04 AMPPASS
Permit finaled under FIR12-00405
FIR12-00133 FIR-Aging Inspection9/27/20129/27/20129/27/2012 8:23:44 AM PASS
Permit finaled under FIR12-00405
BLD12-02291 FIRE-Final Inspection9/26/20129/27/20129/26/2012 1:43:36 PMAPASS
life safety passed