Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02194 Final9/25/20139/27/20139/30/2013 10:13:59 AMPNH
danny Phone #: ###-#### No return phone call
GCE13-00157 GCE-Rough-In9/27/20139/27/20139/27/2013 4:43:17 PMPPASS
Larry ###-#### Rough in ok cover p/s u/g n ok
GCE13-00158 GCE-Rough-In9/27/20139/27/20139/27/2013 4:20:21 PMPPASS
Larry ###-#### Rough in ok cover p/s u/g n ok
ELE13-00603 Final9/27/20139/27/20139/27/2013 3:32:16 PMPPASS
lucas - call 10 mins prior Phone #: ###-#### Final ok
ELE13-02243 Final9/26/20139/27/20139/27/2013 3:14:56 PMPFAIL
mike Phone #: ###-#### Dishwasher not set, Range and dryer recepticals need swapped, and kitchen and bathroom devices need covers
ELE13-02667 Temporary Service9/27/20139/27/20139/27/2013 2:48:19 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman
t/s o/h n ok
ELE13-01719 Final9/27/20139/27/20139/27/2013 2:30:17 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Rick Berry sign final ok
ELE13-01719 Electrical Rough-In9/27/20139/27/20139/27/2013 2:29:43 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Rick Berry Penhouse, upper floor sign rough in ok
ELE13-02676 Final9/26/20139/27/20139/27/2013 2:27:35 PMAPASS
Larry Phone #: ###-#### Final ok
ELE13-02676 Electrical Rough-In9/27/20139/27/20139/27/2013 2:27:16 PMPPASS
Larry Phone #: ###-#### Front light, switch, and receptical outdoor rough in ok
ELE13-01972 Final9/26/20139/27/20139/27/2013 2:13:39 PMPFAIL
Ryan is contact. Thank you! Phone #: ###-#### >> Inspection requested via web by Chris Chesnut
210.8 All bathroom receptical outlets shall have GFCI protection. Powder baths.
210.52(A)(2) Any wall space 24" and wider shall have receptical outlet. Left of upstairs slider.
406.5 All receptical outlets shall have covers. Basement
ELE13-02683 Rough-In Permanent Service9/26/20139/27/20139/27/2013 1:39:43 PMAFAIL
The outside cans have not been wired yet because of the fire bonnets that I need Phone #: ###-#### >> Inspection requested via web by Neal Rumsey 800.24 Communication circuits shall compy with 300.4(G). Where ran through bosred hole with less than 1 1/4" to framing surface cables shall be protected from physical damage by nail plates.
ELE13-02577 Electrical Rough-In9/26/20139/27/20139/27/2013 12:57:56 PMAPASS
Wall Cover. Danny on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen Offices located in N.E. corner. Wall rough in ok cover
ELE13-02678 Electrical Rough-In9/26/20139/27/20139/27/2013 10:54:02 AMAPASS
this is for walls and ceiling cover in this small space call steve with questions thanks Phone #: ###-#### >> Inspection requested via web by Don Lustig Walls and ceiling rough in ok cover
ELE13-02057 Conference9/26/20139/27/20139/27/2013 10:33:08 AMADONE
Levi on site. Phone #: ###-#### >> Inspection requested via web by Buster Bowen Discussed 2 hr fire barrier for temporary feeders feeding fire sprinkler pumps. Maybe some support and strapping issues due to asbestos presence
ELE13-01617 Permanent Service9/26/20139/27/20139/27/2013 9:30:26 AMAFAIL
Robert Foster Phone #: ###-#### Grounding electode conductor shall not be ran through meter.
250.24- Grounding electode conductor shall terminate at the same bus bar as grounded conductor.
250.26- Main bonding jumper shall be installed.
334.30- NM cable shall be secured with in 8" of boxes.
ELE13-02643 Rough-In Permanent Service9/26/20139/27/20139/27/2013 8:46:32 AMAPASS
Phone #: ###-#### >> Inspection requested via web by George Pascua Rough in ok cover p/s o/h n ok