BLD13-02286
| FIRE-Conference | 9/23/2013 | 9/23/2013 | | P | |
|
|
Matt phone #: ###-####
|
FIR13-00126
| INSP-Final Inspection | 9/25/2013 | 9/27/2013 | 9/30/2013 9:34:37 AM | P | PASS |
|
|
Fire alarm permit work passed inspection. Permit finaled.
|
FIR13-00229
| INSP-Final Inspection | 9/25/2013 | 9/27/2013 | 9/30/2013 9:33:25 AM | P | PASS |
|
|
Fire alarm permit finaled
|
FIR13-00212
| INSP-Final Inspection | 9/25/2013 | 9/27/2013 | 9/30/2013 9:32:29 AM | P | NR |
|
|
Not ready for inspection per contractor
|
FIR13-00352
| INSP-Sprinkler Rough-in | 9/26/2013 | 9/27/2013 | 9/27/2013 4:01:35 PM | A | PART |
|
|
Remainder of overhead work okay for ceiling cover.
|
BLD13-01465
| FIRE-Final Inspection | 9/26/2013 | 9/27/2013 | 9/27/2013 3:22:55 PM | A | PASS |
|
|
Fire life safety passed pending one additional fire extinguisher is posted within allowable travel distance at the 1st floor remodel area and one missing EM light is installed per plan at the exit hall 1st floor east side.
|
BLD13-02209
| FIRE-Final Inspection | 9/26/2013 | 9/27/2013 | 9/27/2013 2:44:01 PM | A | PART |
|
|
Ashley please call before going out Phone #: ###-#### Okayed for Temp per conditions discussed with tenant and R. Gervais pending project related fire alarm permit work.
|
BLD12-01894
| FIRE-Final Inspection | 9/26/2013 | 9/27/2013 | 9/27/2013 1:54:55 PM | A | FAIL |
|
|
Post "door to remain..." signage, remove hasp and padlock at the east pair of exit doors, provide approved power source to appliances (remove ext. cord), install planters at the public way adjacent to exit doors per plan review comments. Noted missing handrails per plan sheet deltas at two locations.
|
BLD12-01893
| FIRE-Final Inspection | 9/26/2013 | 9/27/2013 | 9/27/2013 1:48:37 PM | A | FAIL |
|
|
Post fire extinguishers- one in the special use area, one in the storage area, provide "door to remain unlocked..." signage at the main entry/exit, install approved door hardware or remove non-required exit signs at three locations in the storage areas, remove extension cord powering appliances run through the wall and ceilings from the adjacent office space to the storage room.
|
BLD13-02286
| FIRE-Final Inspection | 9/26/2013 | 9/27/2013 | 9/27/2013 10:44:19 AM | A | PASS |
|
|
Fire life safety inspection passed.
|
FIR13-00458
| INSP-Final Inspection | 9/26/2013 | 9/27/2013 | 9/27/2013 10:43:01 AM | A | PASS |
|
|
Final inspection and walkthrough passed, noted adjustments are complete.
|