BLD15-00128
| FIRE-Final Inspection | 9/23/2016 | 9/27/2016 | 9/27/2016 4:13:45 PM | P | CANC |
|
|
Tried calling points of contact, Quenton ###-#### and Paul ###-####, did not receive a call back from either contact, this inspection request cancelled due to no return phone call and a new inspection request will need to be rescheduled.
|
BLD16-01557
| FIRE-Final Inspection | 9/26/2016 | 9/27/2016 | 9/27/2016 3:48:39 PM | A | PASS |
|
|
No fire sprinklers, no monitored fire alarm system, smoke detectors are stand-alone and operational (No fuel fired appliances so smoke detection only), no fire extinguishers required for this occupancy, final life fire inspection passed/complete.
|
FIR16-00608
| INSP-Final Inspection | 9/27/2016 | 9/27/2016 | 9/27/2016 3:20:31 PM | P | CANC |
|
|
Superintendent of project, Steve Phone #: ###-#### scheduled the inspection request, alarm contractor was not notified, alarm vendor needs to be onsite for fire alarm system inspection. This inspection request cancelled and alarm vendor will need to schedule final fire alarm inspection request.
|
FIR16-00427
| INSP-Final Inspection | 9/23/2016 | 9/27/2016 | 9/27/2016 3:09:42 PM | P | FAIL |
|
|
City approved drawings were not on site at time of inspection. Flow switch fire bell was not installed at time of inspection, fire plan review notes specify that the bell needs to be mounted on an exterior wall, close to the street address side of house. Numorous concealed type escutcheons are painted, all escutcheons that were painted after installation need to be replaced. Point of contact on project did not know where the underground supply came into the building, previously noted item for proper coverage above underground supply could not be verified, this will need to be addressed/verified before next inspection.
|
FIR16-00146
| INSP-Sprinkler Rough-in/Hydro | 9/26/2016 | 9/27/2016 | 9/27/2016 11:50:39 AM | A | CANC |
|
|
Inspection request rescheduled for 28SEPT2016 per conversation with point of contact, Jeff ###-####. This inspection request is cancelled.
|
BLD16-03255
| FIRE-Final Inspection | 9/26/2016 | 9/27/2016 | 9/27/2016 11:34:20 AM | A | PASS |
|
|
No fire sprinklers, space does have a fire alarm panel that appears to be a non-permited install from a previous tenant (Only area of coverage for panel is the conference room in tenant space)fire alarm panel was not in service at time of inspection, A?C power is off and batteries are depleted, a fire alarm system is not required for this tenant space, fire extinguisher mounted in a common area with a current inspection tag. Final life fire safety inspection passed/complete
|
FIR16-00435
| INSP-Sprinkler Rough-in | 9/27/2016 | 9/27/2016 | 9/27/2016 10:46:47 AM | P | PASS |
|
|
Tenting inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover.
|
FIR13-00167
| INSP-Sprinkler Rough-in/Hydro | 9/26/2016 | 9/27/2016 | 9/27/2016 9:53:32 AM | P | CANC |
|
|
This inspection request was for 28SEPT2016, this inspection request is cancelled and a new inspection request will be generated for the correct day.
|
BLD16-01644
| FIRE-Final Inspection | 9/26/2016 | 9/27/2016 | 9/27/2016 9:45:13 AM | P | PART |
|
|
Fire sprinkler inspection is complete, partial fire alarm (FIR16-00612) inspection is complete (TCO is authorized per conversation with Scott Arellano, fire alarm install is complete for tenant space, as long as the install matches city approved drawings then FIR16-00612 can be finaled once permit is in issued status), fire extinguishers are in common area's with current inspection tags. Partial life fire safety inspection passed/complete, BLD permit can be finaled on life fire safety permit after fire alarm permit is finaled.
|
FIR16-00612
| INSP-Final Inspection | 9/27/2016 | 9/27/2016 | 9/27/2016 9:39:40 AM | A | PART |
|
|
Partial final for fire alarm inspection is passed/complete, all audio visual devices tested/inspected for area of work. FIR permit for this project is in review status, as long as the city approved drawings match the installation of the tenant space then FIR16-00612 can be finaled once permit is in issued status.
|
FIR16-00424
| INSP-Final Inspection | 9/27/2016 | 9/27/2016 | 9/27/2016 9:36:36 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|