Inspections for the day of: Wednesday, September 27, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00146 INSP-Sprinkler Rough-in9/26/20179/27/20179/27/2017 2:23:50 PMAPASS
Sprinkler piping above the south Restroom is ok for cover
NAF17-00037 INSP-Final9/26/20179/27/20179/27/2017 2:23:03 PMAFAIL
Nothing attempted worked today except the domestic water did shut down upon activation of the flow switch.. To be rescheduled
FIR17-00318 INSP-Final Inspection9/26/20179/27/20179/27/2017 9:29:59 AMAPART
Not ready for a final yet. I need as-builts showing the additional notification devices that have been added for walls that have not been installed yet. If the walls do not get installed then the as-builts need to reflect that. Also the security locks have not been installed on the south side doors for testing/release upon activation of fire alarm. I spoke to Colton with Simplex about this.
FIR17-00261 INSP-Final Inspection9/26/20179/27/20179/27/2017 9:27:44 AMAPART
Not ready for final yet. To final project I need as-builts showing some of the walls deleted. or if the walls will be installed at least two pendant heads will be required at both ends of the short corridor at the south stair well. I spoke to Brad Bettencourt about this.
BLD17-01764 FIRE-Final Inspection9/26/20179/27/20179/27/2017 9:25:11 AMAPASS
life safety passed